Panasonic U-8ME1E8E Service Manual page 79

2way system
Table of Contents

Advertisement

4. Recovering Refrigerant
Refrigerant
recover unit
3
Refrigerant
recovery cylinder
4-3. Recovery of Refrigerant from Entire System
(1) Turn off power to the entire outdoor system.
(2) Short-circuit the AP (Air Purge) pins (CN050) on the outdoor control PCB of all outdoor units, then supply
power to the outdoor units.
* By short-circuiting the AP pins and supplying power to the outdoor units, the solenoid valve in each unit is
forcibly opened and all remaining refrigerant can be recovered.
(3) If any unit has encountered a power failure, follow the instructions in "4-1. Refrigerant Recovery Procedures
(from Outdoor Units)" and perform refrigerant recovery for the faulty outdoor unit.
(4) Connect the manifold gauge to the high- and low-pressure outlet ports (Schrader-type valves) on any outdoor
unit. (Fig. 5)
CAUTION
(5) Connect the manifold gauge valves, refrigerant recovery unit, and refrigerant recovery cylinder. Quickly connect
each part to prevent air from entering the tubing.
(6) Check that each service valve of the gas tubes, liquid tube, and the balance tube for the outdoor unit has
opened, then perform refrigerant recovery.
* If only a single outdoor unit is installed, the balance tube is not used. Therefore, leave this valve closed.
NOTE
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery unit.
Low-pressure outlet port
(for ø7.94mm-dia connector)
High-pressure outlet port
(for ø7.94mm-dia connector)
Manifold gauge
Lo
Hi
Liquid tube service port
(for ø7.94mm-dia connector)
Remaining refrigerant may create internal pressure, therefore care should be
taken when connecting the hoses.
Outdoor Unit Repair Procedures
18HP / 20HP types
Fig. 5-c
3 - 14
2WAY SYSTEM
Gas tube service port
(for ø7.94mm-dia connector)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents