Bosch Rexroth lndraControl VPB 40.1 Project Planning Manual page 68

Control cabinet pc
Table of Contents

Advertisement

66/81
Bosch Rexroth AG
Software
System Health
Enable Temp Control: active
Enable Fan Control: active
Enable Voltage Control: active
Disable UPS: inactive
No Powerdown on Shortbreak: active
Execute Command File: inactive
This tab indicates the current measured values of the internal operating vol‐
tages, the battery voltage, the system temperature and the status of the fan
function.
Fig.9-6:
System Health tab
The value of the battery voltage (Battery Voltage) is only updated after a battery
test. The battery test occurs automatically after a system start and then every
12 hours or after having pressed the Test Battery button.
The LED flashes red, if the value of the battery voltage, which was meas‐
ured under load, is too low.
The LED flashes green, if the battery pack is ready for operation.
NOTICE
Excessive battery tests discharge the battery pack. Do not perform more than
five battery tests within a 24 hour period.
The following applies to the fan monitoring (Fan Speed):
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
Possible damages to the VPB 40.1 and the
connected machines if the UPS functionality is
not guaranteed anymore caused by excessive
battery tests.