Software
System Health
●
Enable Temp Control: active
●
Enable Fan Control: active
●
Enable Voltage Control: active
●
Disable UPS: inactive
●
No Powerdown on Shortbreak: active
●
Execute Command File: inactive
This tab indicates the current measured values of the internal operating vol‐
tages, the battery voltage, the system temperature and the status of the fan
function.
Fig.9-6:
System Health tab
The value of the battery voltage (Battery Voltage) is only updated after a battery
test. The battery test occurs automatically after a system start and then every
12 hours or after having pressed the Test Battery button.
●
The LED flashes red, if the value of the battery voltage, which was meas‐
ured under load, is too low.
●
The LED flashes green, if the battery pack is ready for operation.
NOTICE
Excessive battery tests discharge the battery pack. Do not perform more than
five battery tests within a 24 hour period.
The following applies to the fan monitoring (Fan Speed):
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
Possible damages to the VPB 40.1 and the
connected machines if the UPS functionality is
not guaranteed anymore caused by excessive
battery tests.