Connecting the connecting cable to the shield at the front connector module
The connecting cables have two pre-prepared points for shield connection. These points are
protected by a protective sheath (shrink-on sheath) on delivery, which will need to be
removed at the required place.
Which shield connection point you need depends on the location of the connection in the
front connector module. For connection in the upper position, use the shield connection point
shown in
in
Figure 5-4
Procedure
1. Uncover the cable sheath by removing the protective sheath (shrink-on sheath) at the
2. Push the shield clamp over the connecting cable shield.
3. Connect the connecting cable to the front connector module.
4. Push the shield clamp up over the shield clip to connect the cable shield
SIMATIC TOP connect for S7-1500 and ET200MP
Manual,
. For connection in the upper position, use the shield connection point shown
.
Shield connection in different connection positions
required place.
.
Wiring SIMATIC TOP connect to the I/O modules
5.5 Shield connection of the signal cables
47