① Align the key hole slots in the glides to the T-head pins on both sides of the server, and slide
the mounting glides forward until the pins are secured in the slots.
② Align the two holes on the mounting glide to the threaded standoffs on the front end of the
server.
③ Secure each mounting glide with two of the M3.5 x 5 mm screws with pre-applied adhesive
that come with the vertical mounting kit.
Step 3.
Install one C-channel in the lower portion of the rack cabinet.
Figure 38. Installing the lower C-channel
① Align the C-channel between the lower rack EIA flanges.
② Secure the front end of the C-channel to the front EIA flange with one M5 x 20 mm screw
through the left most hole in the channel.
③ Secure the rear end of the C-channel to the rear EIA flange with two M5 x 20 mm screws
through the right and left most holes in the bracket.
Attention: Do NOT over-tighten the screws as the rack EIA flange could be deformed.
Step 4.
Install the other C-channel in the upper portion of the rack cabinet.
.
Chapter 6
Installing optional kits
33