Advanced; Runtime Parameters - Philips dynalite DDRC-GRMS-E Commissioning Manual

Guest room relay controller
Table of Contents

Advertisement

Signify Classified - Internal

Advanced

Property
Switch
Enable when panel disabled
Trigger at startup
Proxy channel index

Runtime Parameters

Property
Join level
Area link bits
Current preset
March 5, 2019
Description
Enables or disables the selected input.
The Dry Contact inputs (like panel button functions) can be disabled
temporarily to prevent the use of the inputs / panels in a particular
area. Applications include panels in public areas that are only operated
by authorized staff.
Buttons may be enabled/disabled using one of the following
commands:
Logical DyNet Enable/Disable Panel (Opcode 0x15, 0x16)
Physical Task Instruction EnableButton (0xf0,0xf0,0xf0,0xf0)
Logical DyNet Panic/Unpanic (Opcode 0x17, 0x18)
When set to True, this setting prevents the dry contact input from being
temporarily disabled by the above messages to the configured Area(s).
If True, the input will trigger its assigned Function when the controller is
switched on or reset.
Internal system setting, not user-adjustable.
Description
Internal system settings, not user-adjustable. These read-only
parameters are used for diagnosing system issues and can be
refreshed from the device by performing a
DDRC-GRMS-E
.......................................
Commissioning Guide
.......................................
Page 21
.......................................
Load From Device.