Panasonic WH-MHF12G9E8 Service Manual page 108

(mono bloc) air-to-water heat pump system
Hide thumbs Also See for WH-MHF12G9E8:
Table of Contents

Advertisement

16.5.20 Outdoor Fan Motor (DC Motor) Mechanism Locked (F15)
Malfunction Decision Conditions:
The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine
abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm).
Malfunction Caused:
1
Operation stop due to short circuit inside the fan motor winding.
2
Operation stop due to breaking of wire inside the fan motor.
3
Operation stop due to breaking of fan motor lead wires.
4
Operation stop due to fan motor Hall IC malfunction.
5
Operation error due to faulty outdoor unit PCB.
Abnormality Judgment:
Continue 2 times in 30 minutes.