12.1.6 Water Temperature Thermo Shift Setting
Switchs are ignored during "PUMPDW" = ON.
Switchs are ignored during "STATUS" = ON.
"
", "
", "SELECT" switch are ignored if "SETTING" = OFF.
"CANCEL" switch is ignored if "SETTING" = OFF & "STATUS" = OFF.
If "SET" Switch pressed for less than 5secs, immediately enter water temperature shift setting mode.
Once enter this setting mode, "SETTING" display is ON.
This setting mode is used to easily shift the target water outlet temperature.
12.1.7 Outdoor Fan Motor Operation
Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it
stops 30 seconds after compressor stops operation.
Compressor:
Outdoor Fan:
Water
Temp.
H2O LO
H2O HI
OUT LO
OUT LO
= Low outdoor ambient set temperature
OUT HI
= High outdoor ambient set temperature
H2O LO
= Water outlet set temperature at low
outdoor ambient set temperature
H2O HI
= Water outlet set temperature at high
outdoor ambient set temperature
Shift value = Setting water temperature thermo shift
ON
Fan Speed
ON
30 sec
+ 5
± 0
Shift value
- 5
OUT HI
Outdoor
Temp.
OFF
OFF
60
ON
ON