10D1475 MINI-MAG MAGNETIC FLOWMETER INSTRUCTION BULLETIN

3.0 START-UP

The Bailey-Fischer & Porter Series 10D1475 MINI-MAG Magnetic Flowmeter (which includes the
integral or remote Signal Converter) is precision calibrated at the factory for the values stated on the
instrument tag. If specific values were not specified, the meter is calibrated at some nominal
maximum flow rate and for a 4-20 mA current output span. Typical instrument data tags are shown in
Figures 3-1 & 3-2.
There are no operating controls that require field adjustment unless the full scale range setting was
not specified when the meter was ordered. If a change in the full scale range setting is required, refer
to the Instruction Bulletin supplied with the 10D1475H & 10D1475J Signal Converters. If no change
is required, the equipment is ready for operation as received.

FIGURE 3-1. TYPICAL INTEGRAL PRIMARY 10D1475H DATA TAG

FIGURE 3-2. TYP. REMOTE PRIMARY 10D1475H & J DATA TAG

3.1 Preliminary Check List

Follow these start up instructions after completing the assembly and installation of the Primary and
Converter:
• Check that the flow direction of the fluid agrees with the flow-direction arrow
on the primary housing.
• Check that the flowmeter is properly grounded. See Section 2.4. Improper
grounding may result in unsatisfactory performance.
• Check that the interconnections agree with the interconnection diagrams
shown in the instruction bulletins supplied with the Converter.
• Check that the power supply agrees with the specifications on the data tag.
• Check that the ambient conditions meet the conditions specified in Section
1.4 - Specifications.
START-UP
3-1