Bosch CL400 Manual page 60

Hide thumbs Also See for CL400:
Table of Contents

Advertisement

7- -8
General Information Regarding BUEP-E and BUEP19E
Coordination
Controller Type CL500 as PST
Parameter
Word
PW13
Process coordination point
Example
02
H
I/O status
The parameter coordination is composed of a field coordination marker (low
byte) and a process coordination point (high byte).
It is the coordination markers' task to coordinate the execution of an instruc-
tion on the PST. It is executed only if the corresponding coordination event is
'true'; for the CL500, this means, that you must be in the process coordina-
tion point or that the field coordination marker must be set to 1; the same is
applicable to other controllers.
The command 'control central unit' in the CL500 system uses two kinds of
coordination markers:
D Process coordination marker (AKM) and
D for ZS501 and up: Field coordination marker (FKM)
The AKMs are set as follows:
D 00
System STOP status
H
D 01
System RUN status
H
D 02
I/O status
H
D 03
I/O status or STOP
H
D 04
EP
H
D 05
EP or STOP
H
D 06
OM1
H
D 07
OM1 or STOP
H
D FF
No process coordination
H
The FKMs in the special marker area are determined as follows:
D SM16.0 to SM17.7: one-time FKMs
These FKMs are reset by the system after execution of the coordinated
command.
D SM18.0 to SM19.7: permanent FKMs
These FKMs are not reset by the system after execution of the coordi-
nated command.
The FKMs are coded as follows:
D SM16.0 to SM 17.7:
D SM18.0 to SM 19.7:
D No field coordination:
Contents
High Byte
Field coordination marker
FF
H
No coordination marker
FKMs 0
to F
H
H
FKMs 10
to 1F
H
H
FKMs FF
H
1070 072 196-101 (00.06) GB