Input Parameters - Bosch CL400 Manual

Hide thumbs Also See for CL400:
Table of Contents

Advertisement

6- -2
R5CON
6.2.1

Input Parameters

P0
P1
Parameter
Attribute
P0
W
At this parameter, the RSS and the channel number on which the corre-
sponding job was executed, are set.
Parameter
Attribute
P1
W
Valid entries are:
D Job numbers from 16#0000 to 16#7FFF or
D the wildcards 16#FFFF and 16#FFFE
By indicating a job number 16#0000 to 16#7FFF, the user selects a specific
job for which he wants to get an acknowledgement. This way, a specific job
can be controlled.
The given job number is mirrored in the P2 output parameter.
If the 16#FFFE wildcard is specified as a job number, the R5CON function
module acknowledges all jobs of the interface named by P0 that have been
finished without any error up to this moment.
If additional jobs have been finished with errors, the R5CON acknowledges
the faulty job with the highest job number and sends its status and error
codes in the output parameters back. Other possible faulty jobs are not ac-
knowledged by this R5CON call.
If no job is finished, the value 16#FFFF is returned to the output parameter
P2.
If only error-free jobs are finished, all of them are acknowledged and the
value 16#FFFE is returned to the output parameter P2.
If the wildcard 16#FFFF is given in the P1 parameter, the R5CON acknowl-
edges the job that has been processed by the communication module, but
whose acknowledgement has not yet been received. If this is applicable to
more than one job, the one with the highest job number will be acknowl-
edged. Its job number will then be entered in the output parameter P2. All
other jobs will not be acknowledged.
Description
RSS and channel number
Description
Job number (16#0000 to 16#7FFF, 16#FFFE or
16#FFFF)
1070 072 196-101 (00.06) GB