13 F-Parameters And Iparameters; F-Parameters - Bosch Rexroth R-IB IL 24 PSDO 8-PAC Manual

Table of Contents

Advertisement

DOK-CONTRL-ILPSDO8****-AW04-EN-P
Rexroth Inline Module with Safe Digital Outputs R-IB IL 24 PSDO 8-PAC

13 F-Parameters and iParameters

F-Parameter
Default value
F_Source_
-
Address
F_Destination_
-
Address
F_WD_Time
150
F_SIL
SIL 3
F_CRC_Length
3-byte CRC
F_Block_ID
1
F_Par_Version
1
F_iPar_CRC
0
Table 13-1
Overview of the F-Parameters for the module
13.1

F-Parameters

The values indicated in italics in
and cannot be modified manually.
Description
The parameter uniquely identifies the PROFIsafe source address (controller address).
The address is assigned manually.
PROFIsafe destination address (address of the safe device)
The address is assigned manually and the value can be modified.
Make sure that the value set under F_Destination_Address and the value that you have
set via the 10-pos. DIP switch are the same.
Value range: 1 ... 1022
Monitoring time in the safety module.
A valid current safety telegram must arrive from the safe controller within the monitoring
time. Otherwise, the safety module enters the safe state.
The selected monitoring time must be sufficiently high for telegram delays to be tolerated
by the communication, but still ensure a sufficiently fast error response in the event of an
error (e.g., interruption in communication).
Value range: 1 ... 65534, in 1 ms increments
Unit: ms
Safety integrity (SIL according to IEC 61508) of the safety module
WARNING
Safety functions up to SIL 3 can be achieved with the safety module. The safety integrity
level that can actually be achieved depends on the parameterization, the structure of the
sensor, and the cable installation (see
page
41).
This parameter transmits the length of the CRC2 code to be expected in the safety tele-
gram to the safe controller.
Parameter block type identification
1: The parameter block of the F-Parameters contains the F_iPar_CRC parameter.
Version number of the F-Parameter block.
1: Valid for V2 mode
CRC checksum via the iParameters
The value must be greater than 0.
When verifying the safety function, check whether the F_iPar_CRC parameter is greater
than 0 for all devices. If not, check the iParameters and the CRC checksum in the iParam-
eter and F-Parameter.
Bosch Rexroth AG
F-Parameters and iParameters
Table 13-1
are preset by the system
"Connection Examples for Safe Outputs" on
75/94

Advertisement

Table of Contents
loading