The disturbance recordings list shows you the description, date and time of the disturb-
ance. When you want to save the list locally on your computer, select it and download
it by clicking Save. The list is saved in .csv format and can be opened in MS Excel. You
can also delete disturbance recordings from the COM600 computer by clicking Delete.

Parameter setting

Changing parameters

You can view parameter information by clicking on Parameters below the desired IED
in the substation structure, if this functionality is supported by the IED. In this view you
can also change parameter settings.
Click the
icon next to the parameter to open the corresponding help text for each
parameter.
Figure 3.10.1-1 An example of the Parameter Setting view
To change parameter settings:
1.
Click Enable Write on the top of the Parameter Setting view.
2.
Select a new value from the drop down menu or type in a value in the New Value
field. To apply changes, click Write to IED.
3.
If the new values are accepted, the background of the modified parameters turns
green. If the new valuea are incorrect, a message "Some settings are not in correct
range" is displayed and the background of the modified parameters turns red. Type
in values that are in the correct value range.
4.
To manually update the values, click Refresh Values.
5.
After you have made all necessary changes, click Disable Write. If the IED has
been configured with a store option, a store dialog will appear. In the dialog you
can store the parameter changes permanently to the IED non volatile memory. If
you click OK, the parameter changes are stored permanently. If you click Cancel,