Item
Temperature
Relative humidity
Cleanness
ESD prevention
EMI prevention
Lightning
protection
Electricity safety
Workbench
Rack-mounting
requirements
The router is far away from any moist area and heat source.
Safety
precautions
The emergency power switch in the equipment room is located.
Requirements
0°C to 45°C (32°F to 113°F).
5% to 90% (noncondensing).
Dust concentration ≤ 3 × 10
No visible dust on desk within three days.
The equipment and floor are well grounded.
The equipment room is dust-proof.
The humidity and temperature are at a proper
level, respectively.
Wear an ESD-preventive wrist strap and uniform
when touching a circuit board.
Place the removed memory module, CF card, or
interface module on an antistatic workbench, with
the face upward, or put it into an antistatic bag.
Touch only the edges, instead of electronic
components when observing or moving a removed
memory module, CF card, or interface module.
Take effective measures to protect the power
system from the power grid system.
Separate the protection ground of the router from
the grounding device or lightning protection
grounding device as far as possible.
Keep the router far away from radio stations, radar
and high-frequency devices working in high
current.
Use electromagnetic shielding when necessary.
The grounding cable of the chassis is well
grounded.
The grounding terminal of the AC power
receptacle is well grounded.
A port lightning arrester is installed. (Optional.)
A power lightning arrester is installed. (Optional.)
A signal lightning arrester is installed at the input
end of an external signal cable. (Optional.)
Equip an uninterrupted power supply (UPS).
In case of emergency during operation, switch off
the external power switch.
The workbench is stable enough.
The workbench is well grounded.
The rack is equipped with a good ventilation
system.
The rack is sturdy enough to support the weight of
the router and installation accessories.
The size of the rack is appropriate for the router.
The front and rear of the rack are at least 0.8 m
(2.62 ft) away from walls or other devices.