Intermediate Storage - Siemens 8DA Installation Instructions Manual

Medium-voltage switchgear
Table of Contents

Advertisement

Storage in closed rooms
=USNJVOTPKV=G=fkpq^iiqflk=fkpqor`qflkp=Ua^=G=oÉîáëáçå=MP
5.4

Intermediate storage

DANGER!
Risk of injury and damage to the stored goods if the storage surface is overloaded or
the transport units are stakked.
!
Observe the load-bearing capacity of the floor.
!
Do not stack the transport units.
DANGER!
Fire risk!
!
No smoking.
!
Keep fire extinguishers in a weatherproof place and mark their locations.
!
Identify location of the fire extinguisher.
ATTENTION!
Supplied desiccant bags lose their effectiveness if they are not stored in the
undamaged original packings.
!
Do not damage or remove packing of desiccant bags.
!
Do not unpack desiccant bags before use.
ATTENTION!
The transport units may be damaged if these are stored outdoors without seaworthy
packing (seaworthy crate).
!
Store transport units outdoors in seaworthy packing (seaworthy crate) only.
The following switchgear parts must be stored in closed rooms:
• Unpacked parts
• Transport units which are not packed in seaworthy crates
The storage room must have the following characteristics:
• Well-ventilated
• Free of dust
• Dry and protected against flooding
• Relative humidity should not exceed 50%
• Protected against vermin (e.g. insects, mice, rats)
• Even floor to enable stable storage
• Floor with adequate load-bearing capacity
• Sufficient size to enable clearly arranged storage
!
Do not unpack small parts to avoid corrosion and loss.
!
Store transport units in such a way that they can be taken out later in the correct
order for installation.
!
Provide for sufficient ventilation in heated storage rooms.
fåëí~ää~íáçå
9