S15 Application Note 1.8.0
Startup Guide
Setup and program the basic parameters.
A
STEP
Startup Checklist
Visual Inspection
No foreign materials (metal shavings, hardware)
Input and Output Wiring
Input leads are not wired to output terminals
Input, output and control wires are in separate conduit
Motor leads do not share conduit with any other motor leads
Verify input and output wire tightness and condition (continuity, frayed wires, loose connections,
pinched insulation)
Motor Terminal Box
Verify no power factor correction capacitors are installed
Verify wire tightness and condition (continuity, frayed wires, loose connections, pinched insulation)
Drive to Motor Ground Connection (ASD chassis to motor chassis)
Verify wire tightness and condition (continuity, frayed wires, loose connections, pinched insulation)
Record the Electrical Distribution System
Delta/Wye with Grounded Secondary
Grounding Capacitor
□ Enabled □ Disabled
This should be
DISABLED
otherwise it could result in a VFD failure. Refer to Section 1.3.3 of the S15 Instruction Manual E6582175
for more details.
© Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC-ASD@toshiba.com (855) 803-7089 13131 West Little York Road, Houston, TX
on Ungrounded, Corner Grounded or High Impedance Grounding Systems
Estimated Time: 20-30 Minutes
Level: 1
Prerequisite:
S15 Application Note 1.1.0
Navigating Menus & Parameters

Advertisement

loading

Summary of Contents for Toshiba S15

  • Page 1 DISABLED on Ungrounded, Corner Grounded or High Impedance Grounding Systems otherwise it could result in a VFD failure. Refer to Section 1.3.3 of the S15 Instruction Manual E6582175 for more details. © Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC-ASD@toshiba.com (855) 803-7089 13131 West Little York Road, Houston, TX...
  • Page 2 Analog Inputs – Verify polarity. Scaling can be adjusted with parameters F201 to F221. □ VIC (4-20mA) □ VIA (0-10VDC) □ VIB (-10 to +10VDC) © Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC-ASD@toshiba.com (855) 803-7089 13131 West Little York Road, Houston, TX...
  • Page 3 Verify digital input operation □ The S15 has seven digital inputs available and one Safe Torque Off (STO) input. Four of the digital inputs can have more than one function assigned. Digital inputs can be monitored on the keypad in Monitor Mode, refer to S15 Application Note 1.1.0 Navigating Menus &...
  • Page 4 Digital Outputs Verify digital output operation □ The S15 has three outputs available; two relay outputs and one digital output. Two of the outputs can have more than one function assigned. Parameter f139 determines if both functions are required to be true to change state or only one function is required.
  • Page 5: Startup Parameters

    Recommended Carrier Frequency is 4.0kHz. Change f701 before to avoid dealing with percentages. Motor kW and RPM are not necessary to enter in the drive unless performing an auto-tune. Refer to S15 App Note 2.8.0 Motor Auto-tuning. Parameter Description Default Value...
  • Page 6: Model Information

    Record the model information from the nameplate sticker and CPU versions through monitor mode □ Information Details Type Serial No Infromation Details CPU1 Version CPU2 Version © Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC-ASD@toshiba.com (855) 803-7089 13131 West Little York Road, Houston, TX...