Hitachi HX-RIO3 Series User Manual page 23

Hide thumbs Also See for HX-RIO3 Series:
Table of Contents

Advertisement

23
(1) Run '[Hitachi] -> [IOGuidePro] -> [Protocol Messenger] -> [Modbus]'
(2) Write the value of each.
*Protocol : Modbus TCP, Modbus RTU
*ComPort : User Port / Baudrate : 115200(default)
*Address(Hex) : 1600 (IP Address Register)
:: 1602 (IP Subnet Mask Register)
:::1604 (Gate way Register)
*Function(Dec) : 03, Read Holding Registers
(3) After clicking the 'send' button and confirm the necessary information.
If you choose 'ByteDec', easier to see.
:::1610 (Mac Address Register)
HX-RIO3 Series