Analog Input Types
Thermocouple
Maximum Range ºC
B
—18 to 1800
E
—100 to 900
J
—100 to 900
K
—100 to 1300
L
—100 to 900
N
—200 to 1300
R
—18 to 1700
S
—18 to 1700
T
—250 to 300
RTD
Maximum Range ºC
PT100
—200 to 600
2-wire Transmitter Power Supply
Number
1 fitted as standard
Voltage
24 V DC
Drive
Up to 45 mA, i.e. can drive 2 loops
Ethernet
Physical medium
10BaseT
Protocols
TCP/IP, ARP, ICMP, FTP (server), HTTP,
MODBUS TCP (client + server)
FTP server functions
Directory selection and listing
File upload/download
12 configurable users with full or read-only access
Web server functions
Operator
screen
monitoring/selection.
recording channels, analog/digital signals, alarms, totalizers and
archiving
SMTP client compatibility
Compatible with MS Exchange versions up to and including
MS Exchange 2003
IM/SM3000–EN Rev. L
Maximum Range ºF
0 to 3270
—140 to 1650
—140 to 1650
—140 to 2350
—140 to 1650
—325 to 2350
0 to 3000
0 to 3000
—400 to 550
Maximum Range ºF
—325 to 1100
Advanced Math
Math Blocks
Type
12 equations provide ability to perform general arithmetic calculations
including F
emissions calculations
Size
40-character equation
Functions —
+, —, /, log, Ln., Exp, X
standard deviation, high/median/low select, multiplexer, absolute,
relative humidity
Tags
8- and 20-character tags for each block
Update rate
1 enabled block every 100 ms
Logic Equations
Number
12
Remote
monitoring
of
Size
11 elements each
Functions
AND, OR, NAND, NOR, XOR, NOT
Tags
20-character tag for each equation
Update rate
300 ms
Accuracy (% of reading)
0.1 % or ± 2 ºC (3.6 ºF) (above 200 ºC [392 ºF])
0.1 % or ± 0.5 ºC (0.9 ºF)
0.1 % or ± 0.5 ºC (0.9 ºF)
0.1 % or ± 0.5 ºC (0.9 ºF)
0.1 % or ± 1.5 ºC (2.7 ºF)
0.1 % or ± 0.5 ºC (0.9 ºF)
0.1 % or ± 1 ºC (1.8 ºF) (above 300 ºC [540 ºF])
0.1 % or ± 1 ºC (1.8 ºF) (above 200 ºC [392 ºF])
0.1 % or ± 0.5 ºC (0.9 ºF)
Accuracy (% of reading)
0.1 % or ± 0.5 ºC (0.9 ºF)
, mass flow (of ideal gases), relative humidity and
0
, , Sin, Cos, Tan, mean, rolling average,
n