SM3000
Multipoint Videographic Recorder
Fig. 6.7 Exiting Configuration Mode
Note.
Selecting 'Save as Current Configuration' suspends recording for a short time while the new configuration is implemented.
When saving the current configuration to internal storage, it is saved twice, once with the filename 'SM3000.cfg' and again
with the filename '<time><date><instrument tag>.cfg'.
When saving the current configuration to external storage, it is saved with the filename '<time><date><instrument
tag>.cfg'. It is also saved automatically to internal storage with the filename 'SM3000.cfg'.
When 'Save Configuration' is selected, the configuration file is saved with the filename '<time><date><instrument tag>.cfg'
to either selected location, internal or external.
Changes are saved to non-volatile memory only when one of the save options above has been selected. Any powerdown
before this results in lost configuration changes.
Selecting 'Cancel' discards unsaved changes and returns the instrument to the Operating level.
New internal data files for enabled recording channels are created if any of the following configuration parameters are
changed:
Recording channel source
Primary/secondary sample rate
Primary/secondary sample rate source
Input filter type
Engineering range
Channel tag
New internal data files for all enabled recording channels are created if the instrument tag or the number of groups is
changed, or any previously disabled channel is enabled. Any unarchived data is lost.
A warning is displayed if a configuration change will result in new internal data files for enabled recording channels being
created. Select 'Yes' to accept the configuration change. Select 'No' to cancel the configuration change.
60
Configuration change will
cause the internal
recording data files to be
recreated
Configuration change will
not cause the internal
recording data files to be
recreated
6 Configuration