Hitachi CONVENTION 14 Instruction Manual page 79

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

2 − 32
2 32
(Starting point)
Press the
Press the
Press the
Press the
Set the Motor Current – The inverter has thermal overload protection that is designed
to protect the inverter and motor from overheating due to an excessive load. The
inverter's uses the motor's current rating to calculate the time-based heating effect.
This protection depends on using correct current rating for your motor. The level of
electronic thermal setting, parameter B012, is adjustable from 20% to 120% of the
inverter's rated current. A proper configuration will also help prevent unnecessary
inverter trip events.
Read the motor's current rating on its manufacturer's nameplate. Then follow the steps
below to configure the inverter's overload protection setting.
(Starting point)
Press the
Press the
Press the
Press the
Press the
Press the
Press the
Action
key and hold until
1
FUNC
key.
or
key as needed.
2
1
STR
key.
Action
FUNC
key.
1
key.
FUNC
key.
1
key and hold until
FUNC
key.
or
key as needed.
1
2
key.
STR
Display
Func./Parameter
A003
Base frequency setting
A082
AVR voltage select
Default value for AVR voltage:
230
200V class = 230VAC
400V class = 400VAC (HFE)
or
400
Set to your motor specs (your display
215
may be different)
Store parameter, returns to "A"
A082
Group list
Display
Func./Parameter
A082
AVR voltage select
"A" Group selected
A- - -
b- - -
"B" Group selected
b001
First "B" Group parameter selected
b012
Level of electronic thermal setting
Default value will be 100% of
1.60
inverter rated current
Set to your motor specs (your display
1.80
may be different)
Store parameter, returns to "B"
b012
Group list
= 460VAC (HFU)