Page 3
F-400 Fire rated switch-disconnectors — Diagrams Switch-disconnector 3P Switch-disconnector 4P T4(N) L3 L4 Switch-disconnector 6P L3 L1 L2 L3 * Early break * Auxiliary contacts are 25A. Auxiliary contacts identification number change based on the number of switch cells.
Page 4
F-400 Fire rated switch-disconnectors — Wiring Retighten all connection screws during installation 25...40A 2Nm 63...125A 3,5Nm ir e ir e it c it c d is d is Enclosure and cover Attention: earthing IP65 cable glands has 25...63A 1,6Nm to be used section 2,5...16mm...
Page 5