Alarm Reference

Alarm Name
Alarm
Severity
Abnormal
Critical
board comm
Failed to
Critical
configure
board
Board quantity
Critical
inconsistency
Main input
Critical
open phase
Main input
Critical
breaker
tripping
Main input
Critical
overload
Main input
Major
surge
protection
abnormal
Br. circuit
Critical
breaker off
Branch
Critical
overload
Main input br.
Major
current shock
Possible Cause
The monitoring board is
disconnected.
The MDU version does not
match the power distribution
monitoring board.
Monitoring board fault.
The cable has become
loose.
The input power is abnormal.
The back-end is short-
circuited or experiences
overcurrent.
The system is overloaded.
The input AC SPD is
damaged by a lightning strike.
A branch switch has changed
from ON to OFF.
The branch is overloaded.
The insulation of a branch is
abnormal.
10
Solutions
Check whether the control area
network (CAN) cable is in loose
contact. If yes, connect it securely.
Use the latest upgrade package to
activate the board.
Check whether the run indicator
of the monitoring board is steady
on. If no, replace the monitoring
board.
Check whether the CAN cable is
securely connected.
Check the input power.
Check whether the back-end current
is short-circuited or experiences
overcurrent.
Check all output load power.
Replace the input AC SPD.
Check the circuit of the branch.
Check the load power of the branch.
Check the cable insulation of the
output branch.