Huawei PDU8000 Quick Manual page 6

Modular integrated pdc
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

4. Connect the output cables for the PDC.
(1) Connect the power cables of the IT equipment
to the terminals of IT output in the PDC.
(3) Connect the lighting power cables to the lighting output in the PDC.
(2) Connect the power cables of the air
conditioner to the terminals of air conditioner
output in the PDC.
Connect the lighting cables to XT2-1–
XT2-6.
In the MCCB dual-input scenario for
the air conditioner power distribution,
the L wire of the lighting cable is
routed on the right side of the cabinet
rear door, and the N and PE wires of
XT2-4–XT2-6 are routed along the
cabling beam in the middle of the PDC
to the N and PE bars on the left side.