2. INSTALLATION

Remove the drive cover following the inverter instruction manual and
install the option unit using the following procedure:

2.1 Pre-installation Checks

(1) Check the inverter type.
Use the option unit only with an FR-A500(L)/F500(L) series inverter.
Do not use it with any other series (e.g. A200E, A200, A100, Z and F
series). These other series inverters have a different option connector
to prevent installation. If you force the connector, you may damage the
inverter as well as the option unit.
(2) Make sure the inverter input power is off. The option unit can be
damaged if installed with the input power on.
(3) Make sure the PLC master (or PROFIBUS-DP master) is properly
grounded before continuing.

2.2 Mounting Procedure

Hazardous voltage present.
Always isolate power from the inverter and wait 10 minutes until
the bus charge light is off to ensure the charge lamp has gone
out before inserting or removing this option unit or touching the
terminals.
(1) Insert this option unit only into the OPTION PORT# 3 of the inverter.
(2) Carefully insert the connector of the option unit into the connector of
the inverter as shown in Figure 2-1. Use the two mounting holes and
the guide hole to align the bottom board with the matching machine
screw inserts and the plastic guide pin on the inverter. Also be sure to
fit the unit into the option fixing hook (It is available in Aug., 2000).
Make sure that the inverter option is firmly seated in the inverter and
the connector is fully plugged in.
(3) Secure the option unit to the inverter with two mounting screws. If the
screw holes in the option unit do not line up with the inverter mounting
holes, check that the connectors have been fitted correctly.
WARNING