LG multi V ARUB160BT3 Instruction Manual page 22

Table of Contents

Advertisement

Installation
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1) Cut the pipes and the cable.
n Use the accessory piping kit or the pipes purchased lo-
cally.
n Measure the distance between the indoor and the out-
door unit.
n Cut the pipes a little longer than measured distance.
2) Burrs removal
n Completely remove all burrs from the cut cross section
of pipe/tube.
n Put the end of the copper tube/pipe to downward direc-
tion as you remove burrs in order to avoid to let burrs
drop in the tubing.
3) Flaring work
n Carry out flaring work using flaring tool as shown below.
Indoor Unit ca-
pacity
Liquid
[kW(Btu/h)]
[mm(inch)]
≤ 5.6(19,100) Ø6.35(1/4) Ø12.7(1/2) 0~0.5(0.02)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
< 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
≤ 28.0(95,900) Ø9.52(3/8) Ø22.2(7/8)
Firmly hold copper tube in a bar(or die) as indicated dimen-
sion in the table above.
4) Check
n Compare the flared work with figure below.
n If flare is noted to be defective, cut off the flared section
and do flaring work again.
22
Outdoor Unit
Pipe
"A"
Gas
Liquid
[mm(inch)]
[mm(inch)]
0.5(0.02)
~0.8(0.03)
0.5(0.02)
~0.8(0.03)
0.5(0.02)
~0.8(0.03)
Copper
tube
Point down
Gas
Bar
[mm(inch)]
0.5(0.02)
~0.8(0.03)
0.8(0.03)
~1.0(0.04)
Copper pipe
1.0(0.04)
~1.3(0.05)
1.0(0.04)
~1.3(0.05)
Smooth all round
Even length
all round
Slanted Uneven Rough
90
Pipe
Reamer
Handle
Bar
"A"
Clamp handle
Red arrow mark
Inside is shining without scratches.
= Improper flaring =
Inclined
Surface
Cracked Uneven
damaged
Yoke
Cone
thickness

Advertisement

Table of Contents
loading

Table of Contents