LG multi V ARUB160BT3 Instruction Manual page 83

Table of Contents

Advertisement

2) Zoning setting
- Set the address of the valve of the HR unit to the central control address of the connected indoor unit.
- SW01M : selection of the valve to address
SW03M : increase in the digit of 10 of valve address
SW04M : increase in the last digit of valve address
SW05M :Rotary S/W
- Prerequisite for manual valve addressing : central control address of each indoor unit must be preset
differently at its wired remote control.
SW01M
SW03M
SW04M
0
SW05M
S/W No.
No.1
Manual addressing of valve #1
No.2
Manual addressing of valve #2
No.3
Manual addressing of valve #3
No.4
Manual addressing of valve #4
SW03M
Increase in the digit of 10 of valve address
SW04M
Increase in the last digit of valve address
SW05M
Manual addressing of zoning indoor units
HR Unit PCB
Setup
Installation Manual 83