SINAMICS G120 Control Units CU240B-2 Control Units CU240E-2 Parameter Manual · 01/2011 SINAMICS...
Page 3
Parameters Function diagrams SINAMICS Faults and Alarms SINAMICS G120 Appendix Control Units CU240B/E-2 List of Abbreviations Parameter Manual Index Valid for Firmware version Control Units CU240B-2 CU240B-2 DP CU240E-2 CU240E-2 DP CU240E-2 F CU240E-2 DP F A5E02631767B AC 01/2011...
Page 4
Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Page 9
Access level Indicates the level of user access. For the parameters of all variants of Control Units CU240B-2 and CU240E-2 there is only one freely accessible access level effective. The parameters with the declaration "Access level 1“ to "Access level 3“...
Page 49
Description: Enter the inductance of a filter connected at the power unit output. Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power unit. Refer to: p0230 Note: When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIE- MENS filter or to zero.
Page 107
= 12 (start transferring the device master data (GSD) to the memory card) --> The files that are relevant for the communication configuration are transferred from the device memory to the memory card and stored in the /SIEMENS/SINAMICS/DATA/CFG directory. Value:...
Page 108
= 12 (start transferring the device master data (GSD) to the memory card) --> The files that are relevant for the communication configuration are transferred from the device memory to the memory card and stored in the /SIEMENS/SINAMICS/DATA/CFG directory. Value:...
Page 226
If bit 2 = 1, then bit 3 is automatically set to 1. Manual de-selection is possible and may be sensible if the saturation characteristic (p1960) was not measured for third-party motors. Generally, for standard SIEMENS motors, the already pre-assigned (default value) saturation characteristic is adequate.
Page 227
If bit 2 = 1, then bit 3 is automatically set to 1. Manual de-selection is possible and may be sensible if the saturation characteristic (p1960) was not measured for third-party motors. Generally, for standard SIEMENS motors, the already pre-assigned (default value) saturation characteristic is adequate.
Page 324
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associ- ated with a selected Siemens catalog motor are not overwritten. If a catalog motor has not been selected (see p0300), then the following parameters are reset with p3900 > 0 in order to restore the situation that applied when commissioning the drive for the first time: for induction motors p0320, p0352, p0362 ...
Page 494
Parameters Connectors Binectors Data sets Meaning Symbol Symbol Meaning Symbol Meaning Symbol Meaning pxxxx[C] Parameter name [Unit] Monitoring parameter with Parameter name Connector input CI with Parameter name Binector input BI with with Parameter belongs to the rxxxx[y..z] unit [Unit] and index range index range [y..z] index range [y..z] or data set Command Data Set (CDS).
Page 495
Symbols for logic functions Symbols for computational and closed-loop control functions Logical inversion Threshold value switch 1/0 AND element with logical inversion of an input Outputs at y a logical "1" if x < S. & signal OR element Threshold value switch 0/1 Exclusiv-OR/XOR Outputs at y a logical "1"...
Page 496
Switch-on delay Switch symbol 2nd-order filter (bandstop/general filter) pxxxx pxxxx Simple changeover switch Natural frequency, Damping, numerator numerator The switch position is shown according to fn_z pxxxx the factory setting pxxxx pxxxx (in this case, switch position 1 in the default The digital signal x must have the value "1"...
Page 497
Handling BICO technology Binector: r0723.15 Connectors are "analog signals" that can be freely interconnected (e.g. percentage variables, speeds or torques). Connector: r0723 Connectors are also "CO:" display parameters (CO = Connector Output). Parameterization: At the signal destination, the required binector or connector is selected using appropriate parameters: "BI:"...
Function diagrams Input/Output Terminals Input/Output Terminals Function diagrams 2221 – CU240B-2: Digital inputs, electrically isolated (DI0 ... DI3) 2-507 2220 – CU240E-2: Digital inputs, electrically isolated (DI0 ... DI5) 2-508 2223 – CU240B-2: Analog inputs as Digital inputs (DI11) 2-509 2222 –...
Page 507
CU DI Status r0722 Kl.8 Kl.8 Kl.8 p0796.3 r0722 <1> <1> Kl. = Terminal Sampling time of the DI : 2 ms External Interfaces Function diagram FP_2221_97_02.vsd - 2221 - Digital inputs, electrically isolated (DI0 DI3) G120 CU240B-2 13.12.2010 V4.4...
Page 508
External power supply 24 V DC Kl.9 Kl.9 +24 V OUT +24 V OUT Kl.28 Kl.28 <1> 1 = Simulation on CU DI simulation Kl.69 DI COM Kl.69 DI COM Kl.69 DI COM CU DI status inv p0795 CU DI t_debounce DI COM2 DI COM2 DI COM2...
Page 509
CU DI status r0723 Kl.4 AI0- r0722 p0796.11 r0722 <1> Kl. = Terminal Sampling time of the DI : 4 ms External Interfaces Function diagram FP_2223_97_02.vsd - 2223 - Analog inputs as Digital inputs (DI11) G120 CU240B-2 13.12.2010 V4.4...
Page 510
For Example: <1> Kl.1 +10 V OUT Kl.2 1 = Simulation on CU DI Simulation 1.6 V 4.0 V p0795 CU DI t_debounce p0724 r0721.11 CU DI Status inv Kl.3 AI0+ (DI11) r0723 CU DI Status r0723 Kl.4 AI0- r0722 p0796.11 r0722 p0795.12...
Page 511
CU DO status CU S_src DO 0 r0747 <2> p0730 (52.3) Kl.18 Kl.19 Kl.20 Sampling time of the DO : 2 ms <2> Kl. = Terminal External Interfaces Function diagram FP_2231_97_02.vsd - 2231 - Digital output (DO0) G120 CU240B-2 13.12.2010 V4.4...
Page 512
CU DO inv p0748 CU DO status CU S_src DO 0 r0747 <2> p0730 (52.3) Kl.18 Kl.19 Kl.20 CU DO inv p0748 CU DO status CU S_src DO 1 r0747 p0731 (52.7) 24 V Kl.21 Kl.22 CU DO inv p0748.2 CU DO status CU S_src DO 2 r0747...
Page 513
For p0756 = 2, 3 the units are mA. Sampling time of the AI : 4 ms For p0756 = 0, 1, 4 the units are V. Kl. = Terminal External Interfaces Function diagram FP_9567_97_02.vsd - 9567 - Analog input 0 (AI0) G120 CU240B-2 13.12.2010 V4.4...
Page 514
<2> <3> <4> CU AI type 0 ... 8 p0756[0..1] (4) CU WireBrkThresh CU wire brk t_del CU AI status word 0.00 ... 20.00 CU AI sim_mode 0 ... 1000 [ms] r0751 p0761[0..1] (2.00) 0 ... 1 p0762[0..1] (100) p0797[0..1] (0) 20 mA F03505 20 mA...
Page 515
The input signals are referred to the reference quantities p2000 ... r2004 (100 % = p200x). Sampling time of the AO : 4 ms External Interfaces Function diagram FP_9573_97_02.vsd - 9573 - Analog output 0 (AO0) G120 CU240B-2 13.12.2010 V4.4...
Page 516
CU AO outp_val [%] <4> CU AO char x1 CU char x2 r0772 CU AO type -1000.00 ... 1000.00 [%] -1000.00 ... 1000.00 [%] 0 ... 2 p0779 (100.00) CU AO absVal act CU AO T_smooth p0777 (0.00) [0] (0) [0] (100) p0776 (0) [0] (0)
Page 519
Fieldbus t_monit Monitoring functions 0 ... 1999999 [ms] p2040 (100) Cyclic telegrams from the master Fieldbus configuration Field bus baud 4 ... 13 4 ... 13 F01910 "Fieldbus IF: setpoint timeout" p2020 (8) Field bus address No telegrams from the master 0 ...
Page 520
Signal targets for fieldbus STW1 (p0700 = 6) [Function diagram] [Function diagram] Interconnection Signal Meaning Inverted internal control word signal target parameters = ON (pulses can be enabled) STW1.0 p0840[0] = r2090.0 [2501.3] Sequence control 0 = OFF1 (braking with ramp-function generator, then pulse cancellation & ready for switching on) 1 = No OFF2 (enable is possible) STW1.1 p0844[0] = r2090.1...
Page 521
Signal sources for fieldbus ZSW1 (p0700 = 6) Inverted Interconnection [Function diagram] [Function diagram] Signal Meaning signal target <1> parameters internal control word ZSW1.0 p2080[0] = r0899.0 [2503.7] 1 = Ready for switching on Sequence control ZSW1.1 1 = Ready for operation (DC link loaded, pulses inhibited) p2080[1] = r0899.1 [2503.7] Sequence control...
Page 522
r2090.0 PZD1 recv bitw r2090.15 PZD1 recv bitw <1> PZD receive word 1 r2050 PZD recv word r2091.0 PZD2 recv bitw r2091.15 PZD2 recv bitw r2050 <2> PZD receive word 2 PZD recv word r2092.0 PZD3 recv bitw r2092.15 PZD3 recv bitw Fieldbus r2050 PZD receive word 3...
Page 523
Diag send word r2053 [0 7] p2051 [0] PZD send word <1> PZD send word 1 <1> p2051 [1] PZD send word PZD send word 2 <2> p2051 [2] PZD send word PZD send word 3 p2051 [3] PZD send word PZD send word 4 Send telegram p2051 [4]...
Page 526
A01901 "PROFIBUS: Parameterizing telegram incorrect" Diagnostic parameters <1> The response monitoring time t_An is automatically defined by the configuration tool (e.g. HW Config made by Siemens) within the framework of PROFIBUS configuration. PROFIdrive / PROFIBUS Function diagram FP_2410_97_61.vsd - 2410 -...
Page 527
<1> PD Telegr_sel 1 ... 999 p0922 (1) Standard telegrams Manufacturer-specific telegrams Free telegram Interconnec- [2440] [2450] automatically tion is made according to Telegram PZD1 STW1 ZSW1 STW1 ZSW1 STW1 ZSW1 STW1 ZSW1 STW1 ZSW1 STW1 ZSW1 STW1 <4> ZSW1 <4> PZD2 NSOLL_A NIST_A...
Page 528
<2> Data type according to to the PROFIdrive profile: I16 = Integer16, U16 = Unsigned16. <3> Display parameters for receive data according to [2460]. <4> Only SIEMENS telegram 350 PROFIdrive / PROFIBUS Function diagram FP_2440_97_61.vsd - 2440 - PZD receive signals interconnection G120 CU240B/E-2 DP 13.12.2010...
Page 529
Signal targets for STW1 in Interface Mode VIK-NAMUR (p2038 = 2) <1> Interconnection [Function diagram] [Function diagram] Meaning Signal Inverted parameters internal control signal target word = ON (pulses can be enabled) STW1.0 p0840[0] = r2090.0 [2501.3] Sequence control 0 = OFF1 (braking with ramp-function generator, then pulse cancellation & ready for switching on) 1 = No OFF2 (enable is possible) STW1.1 p0844[0] = r2090.1...
Page 530
Signal targets for STW1 in Interface Mode SINAMICS (p2038 = 0) <1> [Function diagram] [Function diagram] Interconnection Signal Meaning Inverted internal control word signal target parameters = ON (pulses can be enabled) STW1.0 p0840[0] = r2090.0 [2501.3] Sequence control 0 = OFF1 (braking with ramp-function generator, then pulse cancellation & ready for switching on) 1 = No OFF2 (enable is possible) STW1.1 p0844[0] = r2090.1...
Page 531
Signal targets for STW3 in Interface Mode SINAMICS (p2038 = 0) <1> Interconnection [Function diagram] [Function diagram] Signal Meaning Inverted internal control word signal target parameters STW3.0 p1020[0] = r2093.0 [3010.2] [3010.2] 1 = Fixed setp bit 0 STW3.1 1 = Fixed setp bit 1 p1021[0] = r2093.1 [2513.2] [3010.2]...
Page 532
Signal sources for PZD send signals PZD send word 1...8 <1> PROFIdrive send p2051[0...7] WORD PROFIdrive Interconnection Function telegram Signal Scaling Description Data type r2053[0...7] WORD Signal No. parameter diagram ZSW1 Status word 1 r2089[0] [2452] Header NIST_A Actual speed A (16 bit) r0063[0] 4000 hex p2000...
Page 533
Signal sources for ZSW1 in Interface Mode VIK-NAMUR (p2038 = 2) <1> Interconnection [Function diagram] [Function diagram] Inverted Signal Meaning parameters internal control word signal target <2> ZSW1.0 1 = Ready for switching on p2080[0] = r0899.0 [2503.7] Sequence control ZSW1.1 1 = Ready for operation (DC link loaded, pulses inhibited) p2080[1] = r0899.1...
Page 534
Signal sources for ZSW1 im Interface Mode SINAMICS (p2038 = 0) <1> Inverted Interconnection [Function diagram] [Function diagram] Signal Meaning signal target <2> parameters internal control word ZSW1.0 p2080[0] = r0899.0 [2503.7] 1 = Ready for switching on Sequence control ZSW1.1 1 = Ready for operation (DC link loaded, pulses inhibited) p2080[1] = r0899.1...
Page 535
Signal sources for ZSW3 im Interface Mode SINAMICS (p2038 = 0) <1> Interconnection [Function diagram] [Function diagram] Inverted Signal Meaning parameters internal status word signal source 1 = DC brake active [7017.5] ZSW3.0 [2511.7] 0 = DC brake not active ZSW3.1 1 = |n_act| >...
Page 536
r2090.0 PZD1 recv bitw r2090.15 PZD1 recv bitw PZD receive word 1 r2050 <1> PZD recv word r2091.0 PROFIBUS PZD2 recv bitw r2091.15 PZD2 recv bitw r2050 PZD receive word 2 PZD recv word r2092.0 PZD3 recv bitw r2092.15 PZD3 recv bitw PROFIdrive r2050 PZD receive word 3...
Page 537
Diag send word r2053 [0 7] p2051 [0] PZD send word <1> PZD send word 1 <1> p2051 [1] PZD send word PZD send word 2 p2051 [2] PZD send word PROFIdrive send PZD send word 3 telegram p2051 [3] PZD send word Header PZD send word 4...
Page 540
PROFIdrive-Bit STW seq_ctrl OFF2 S_src 1 r0898 p0844 [C] Control word sequence control (r0898) <2> r0898 <3> ON / OFF (OFF1) p0840 [C] OFF2 S_src 2 = ON <3> (722.0) r0898.0 To the control unit p0845 [C] 0 = OFF1 active 1 = Operating condition, no coast down active (OFF2 inactive) To the control unit r0898.1...
Page 541
PROFIdrive-Bit ZSW seq_ctrl r0899 Bit No. Status word sequence control (r0899) r0899 From the control unit 1 = Ready for switching on r0899.0 From the control unit 1 = Ready for operation (DC link loaded, pulses inhibited) r0899.1 From the control unit 1 = Operation enabled (drive follows n_set) r0899.2 From the control unit...
Page 542
STW setpoint chan r1198 Bit No. Control word, setpoint channel (r1198) r1198 n_set_fixed Bit 0 p1020 [C] 1 = Fixed setpoint, bit 0 r1198.0 To fixed speed setpoints [3010.2] n_set_fixed Bit 1 p1021 [C] 1 = Fixed setpoint, bit 1 r1198.1 To fixed speed setpoints [3010.2] n_set_fixed Bit 2 p1022 [C]...
Page 543
ZSW 1 r0052 Bit No. Status word 1 (r0052) r0052 r0899 ZSW seq_ctrl [2503.7] 1 = Drive ready for switching on r0899 r0052.0 0 = Drive not ready for switching on r0899 [2503.7] ZSW seq_ctrl 1 = Drive ready for operation (DC link loaded, pulses disabled) r0899 r0052.1 0 = Drive not ready for operation...
Page 544
ZSW 2 r0053 Bit No. Status word 2 (r0053) r0053 r1239 [7017.5] DCBRK ZSW 1 = DC brake active r1239 r0053.0 0 = DC brake not active r2197 [2534.7] ZSW monitor 1 1 = |n_act| > p1226 (n_standstill) r0053.1 r2197 r2197 [2534.7] ZSW monitor 1...
Page 545
STW 1 OFF2 S_src 1 r0054 Bit No. Control word 1 (r0054) p0844 [C] r0054 STW seq_ctrl ON / OFF (OFF1) p0840 [C] [2501.7] r0898 OFF2 S_src 2 0 = OFF1, Shutdown via ramp, followed by pulse disable Sequence control (722.0) r0898 Setpoint channel...
Page 546
Suppl STW r0055 Bit No. Control word 2 (r0055) r0055 r1198 [2505.7] STW setpoint chan r1198 1 = Fixed setp bit 0 Fixed frequencies r1198 [2505.7] STW setpoint chan r1198 1 = Fixed setp bit 1 Fixed frequencies r1198 [2505.7] STW setpoint chan Fixed frequencies r1198...
Page 547
STW n_ctrl r1406 Control word, speed controller (r1406) Bit No. r1406 Reserved Reserved Reserved Reserved n_ctrl integ stop p1476 [C] 1 = speed controller, hold I component r1406.4 To the speed controller [6040.4] n_ctrl integ set p1477 [C] 1 = speed controller, set I component r1406.5 To the speed controller [6040.4] Reserved...
Page 548
ZSW n_ctrl r1407 Bit No. Status word, speed controller (r1407) r1407 1 = V/f control active r1407.0 From the changeover, closed-loop control types 1 = Sensorless operation active r1407.1 1 = Torque limit reached (without pre-control) r1406 1 = Torque control [2520.7] r1406 To speed setpoint, droop [6030.5]...
Page 549
ZSW cl-loop ctrl r0056 Bit No. Status word closed-loop control (r0056) r0056 1 = Initialization completed r0056.0 1 = De-magnetization completed r0056.1 1 = Pulses enabled r0056.2 1 = Soft starting available <1> r0056.3 1 = Magnetization completed [6722.6] r0056.4 1 = Starting boost active r0056.5 1 = Acceleration voltage active...
Page 550
ZSW I_ctrl r1408 Bit No. Status word closed-loop current control (r1408) r1408 1 = Closed-loop current control active r1408.0 [6714.5] 1 = Id controller I comp. limitation r1408.1 Reserved [6714.8] 1 = Voltage limitation r1408.3 Reserved Reserved Reserved Reserved Reserved Reserved r1408.10 [6730.3]...
Page 551
ZSW monitor 1 r2197 Bit No. Status word, monitoring functions 1 (r2197) r2197 From extended signals [8020.8] 1 = |n_act| <= n_min p1080 r2197.0 <1> From speed signals [8010.8] 1 = |n_act| <= speed threshold value 2 (p2155) r2197.1 1 = |n_act| > speed threshold value 2 (p2155) <1>...
Page 552
ZSW monitor 2 r2198 Bit No. Status word, monitoring functions 2 (r2198) r2198 1 = |n_act| <= speed threshold 5 [8021.8] r2198.0 From extended signals From extended signals [8021.8] 1 = |n_act| > speed threshold 5 r2198.1 From extended signals [8021.8] 1 = |n_act| <= speed threshold 6 r2198.2...
Page 553
PROFIdrive-Bit ZSW monitor 3 r2199 Bit No. Status word, monitoring functions 3 (r2199) r2199 From speed signals [8010.8] r2199.0 1 = |n_act| < speed threshold value 3 (p2161) <1> From speed signals [8010.8] 1 = f or n comparison value reached or exceeded (p2141) r2199.1 Reserved Reserved...
Page 560
Changing safety parameters Safety commissioning mode SI act chksm P1 SI setp_chksm P1 [2802.1][2810.3] r9798 p9799 --> select STO <3> <1> Safety parameterizing enable Safety Integrated commissioning p0010 = 95 Safety parameters Safety parameters Enter password SI password inp & &...
Page 561
Safety Integrated version Monitoring clock cycle SI version Drv P1 SI mon_clk cyc P1 [ms] r9770 r9780 F01611 Safety monitoring functions F30611 [2810.3] STO terminal P1 (r0722.4) 1 = Faults with response "NONE" STOP F [2810.1] STO terminal P2 (r0722.5) SI status P1 r9772 [2804.2]...
Page 562
Status word Safety Integrated Status word Safety Integrated Status word Safety Integrated Processor 1 Processor2 Processor 1 and Processor 2 SI status P1 SI Status P2 SI status P1+P2 r9772 r9872 r9773 Bit No. Status (Processor 1) Bit No. Status (Processor 2) Bit No.
Page 563
A01699 Control Unit Power Module +24 V SI status P1 "Shutdown SI FrcdCkProcTimer Processor 1 [2804.1] r9772 paths must 0.00 ... 9000.00 [h] be tested" p9659 (8.00) r9772 SI status P1 1 = STO selected on P1 SI status P1+P2 SI status P1 [2804.1] r9772...
Page 564
SI STO t_debou P1 Kl.9 0.00 ... 100.00 [ms] +24V OUT p9651 (1.00) [2810.4] Kl.16 Kl.69 DI COM & F-DI0 Kl.17 Kl.34 DI COM2 Kl.28 SI STO t_debou P2 0.00 ... 100000.00 [μs] p9851 (0.00) F-DI: Fail-safe Digital Input Safety Integrated Function diagram FP_2812_97_63.vsd - 2812 -...
Page 565
SI Mtn ramp t P1 SI Mtn rp t_del P2 SI Mtn ramp ref P1 SI Mtn ramp ref P2 10.00 ... 99000.00 [ms] 10000.00 ... 99000000.00 [μs] 600.0000 ... 24000.0000 [1/min] 600.0000 ... 24000.0000 [1/min] p9582 (250.00) p9382 (250000.00) p9581 (1500.0000) p9381 (1500.0000) SI Mtn integ STW...
Page 566
SI Mtn integ stat r9722 [2840.4] r9722 SS1 active SI Mtn ramp ref P1 SI Mtn rp t_mon P1 600.0000 ... 24000.0000 [1/min] 0.50 ... 1000.00 [s] SI Mtn ramp t P1 p9581 (1500.0000) p9583 (10.00) 10.00 ... 99000.00 [ms] p9582 (250.00) SI Mtn integ STW r9720...
Page 567
Status word Safety Integrated Status word Safety Integrated Status word Safety Integrated Prozessor 1 Prozessor2 Prozessor 1 and Prozessor 2 SI status P1 SI Status P2 SI status P1+P2 r9772 r9773 r9872 Bit No. Bit No. Bit No. Status (Processor 1) Status (Processor 2) Status (Processor 1 + Processor 2) r9772...
Page 568
SI Mtn integ STW SI Mtn integ stat r9720 r9722 Bit No. PROFIsafe control word Bit No. PROFIsafe status word r9720 r9722 [2855.3] 1 = STO deselection r9720.0 [2855.3] [2855.5] 1 = STO active r9722.0 [2855.5] 1 = SS1 deselection 1 = SS1 active [2855.3] r9720.1...
Page 570
SI discrp t_mon P1 SI discr t_mon P2 1.00 ... 2000.00 [ms] 1.00 ... 2000.00 [ms] p10002 (500.00) p10102 (500.00) SI DI t_debounceP1 Kl.9 0.00 ... 100.00 [ms] SI DI status P1 +24V OUT p10017 (1.00) r10051 r10051 C01770 Discrepancy error Kl.5 F-DI0 F-DI0...
Page 571
F-DI assignment SI Motion Statically active [Source plan] F-DI0 [2850.8] F-DI1 [2850.8] SI Mtn integ stat F-DI2 STO active [2850.8] r9722 [2840.8] Statically inactive r9722 [Source plan] SI Mtn integ STW Deselection STO SI STO F-DI P1 r9720 0 ... 255 SS1 active [2840.4] [2840.8]...
Page 575
Data save active The setpoint for the motorized potentiometer is not saved and after ON is entered using p1040. The setpoint for the motorized potentiometer is saved in a ashion after OFF and after ON set to the saved value. Automatic mode Without ramp generator in automatic mode (ramp-up/ramp-down time = 0).
Page 576
<1> STW seq_ctrl PcCtrl active p1055 r0898 r0807.0 r0898 [2501.7] [2501.2] Setpoint from external OP or operating tool STW seq_ctrl p1056 r0898 r0898 [2501.7] Main setpoint eff [1/min] Total setpoint eff [1/min] r1073 Main setpoint r1078 p1070 [C] <4> (755[0]) Total setp Jog 1 n_set p1109 [C]...
Page 577
STW setpoint chan STW setpoint chan STW setpoint chan r1198 p1113 r1198 p1111 r1198 p1110 r1198 r1198 r1198 [2505.2] [2505.2] [2505.2] 1 = Direction reversal 1 = Inhibit negative direction of 1 = Inhibit positive direction of rotation rotation n_limit setp 0.000 ...
Page 583
Linear U_output max [Veff] U_output max r0071 r0071 Mot U_rated p0304 Op/cl-lp ctrl_mode ECO Mode r1348 0 ... 22 Mot f_rated p1300 [D] (0) U/f Eco fac act v [%] Flux current control (FCC) Dependent on the load 0.00 ... 650.00 [Hz] current p0310 [D] (0.00) U_output max [Veff]...
Page 603
Power Module Control Unit Vdc act val [V] [6723.1] r0070 DC link voltage [6799.1] U_output [Veff] Pulse enable HW r0072 Modulat_depth [%] [6799.1] r0074 U_set [6799.1] [1690.8] U_angle [6714.8] ZSW cl-loop ctrl Gain res_damp p1740 r0056 r0056 f_Slip [2526.2] r0065 Current model Vibration damping...
Page 604
Control Unit Power Module Vdc act val [V] [6724.1] r0070 DC link voltage [6799.1] U_output [Veff] Pulse enable HW r0072 Modulat_depth [%] [6799.1] r0074 U_set [6799.1] [6714.8] U_angle [6714.8] ZSW cl-loop ctrl Gain res_damp r0056 p1740 r0056 [2526.2] Current model Vibration damping f_outp [Hz] r0066...
Page 605
Modulat_depth [%] n_set before filt. [1/min] [6730.4] Mod_depth smth [%] n_set smth [1/min] r0074 r0060 r0020 r0028 100 ms [6731.4] 100 ms n_act [1/min] n_act smooth [1/min] Id_act [Aeff] Id_act smooth [Aeff] [6730.1] r0063 r0021 [6714.8] r0076 r0029 100 ms 300 ms T_smth display p0045...
Page 607
Run-time group RTG sampling time [ms] r20001[1] = 8 ms r20001[2] = 16 ms r20001[3] = 32 ms r20001[4] = 64 ms r20001[5] = 128 ms r20001[6] = 256 ms r20001[0..9] Logic function blocks AND, OR, XOR, NOT Arithmetic function blocks ADD, SUB, MUL, DIV, AVA, NCM, PLI Time function blocks MFP, PCL, PDE, PDF, PST...
Page 608
AND 0 AND 2 AND 0 RTG AND 2 RTG 1 ... 9999 1 ... 9999 p20032 (9999) p20040 (9999) AND 0 inputs AND 2 inputs p20030 p20038 AND 0 output Q AND 2 output Q r20031 r20039 AND 0 RunSeq AND 2 RunSeq 0 ...
Page 609
OR 0 OR 2 OR 0 RTG OR 2 RTG 1 ... 9999 1 ... 9999 p20048 (9999) p20056 (9999) OR 0 inputs OR 2 inputs p20046 p20054 OR 0 output Q OR 2 output Q r20047 r20055 OR 0 RunSeq OR 2 RunSeq 0 ...
Page 611
NOT 0 NOT 3 NOT 0 RTG NOT 3 RTG 1 ... 9999 1 ... 9999 p20080 (9999) p20092 (9999) NOT 0 input I NOT 3 input I p20078 NOT 0 inv output p20090 NOT 3 inv output r20079 r20091 NOT 0 RunSeq NOT 3 RunSeq 0 ...
Page 612
ADD 0 RTG ADD 0 5 ... 9999 p20096 (9999) ADD 0 inputs SUB 0 p20094 ADD 0 output Y SUB 0 RTG r20095 5 ... 9999 p20104 (9999) SUB 0 inputs ADD 0 RunSeq p20102 SUB 0 difference Y 0 ...
Page 613
MUL 0 DIV 0 DIV 0 RTG MUL 0 RTG 5 ... 9999 5 ... 9999 p20121 (9999) p20112 (9999) MUL 0 inputs DIV 0 quotient DIV 0 inputs p20110 DIV 0 Quotient r20119 p20118 MUL 0 product Y DIV 0 Multiple integer quotient r20111 DIV 0...
Page 614
AVA 0 AVA 0 RTG 5 ... 9999 p20131 (9999) AVA 0 output Y AVA 0 input X p20128 r20129 AVA 0 input neg SN r20130 AVA 0 RunSeq 0 ... 32000 p20132 (340) AVA 1 AVA 1 RTG 5 ... 9999 p20136 (9999) AVA 1 output Y AVA 1 input X...
Page 619
PDF 0 PDF 2 PDF 0 RTG PDF 0 t_ext ms PDF 2 RTG PDF 2 t_ext ms 5 ... 9999 0.00 ... 60000.00 5 ... 9999 0.00 ... 60000.00 p20171 (9999) p20169 (0.00) p20347 (9999) p20345 (0.00) PDF 0 inp_pulse I PDF 2 inp_pulse I p20168 PDF 0 output Q...
Page 630
Tec_ctrl sel bit 0 p2220 [C] 0 ... 15 Tec_ctrl sel bit 1 Tec_ctrl No. act 0.00 % 0 0 0 0 r2229 p2221 [C] Tec_ctr fix val 1 -200.00 ... 200.00 [%] 0 0 0 1 Tec_ctrl sel bit 2 p2201 [D] (10.00) p2222 [C] Tec_ctr fix val 2...
Page 631
Tec_ctrl sel bit 0 p2220 [C] Tec_ctrl sel bit 1 p2221 [C] Tec_ctr FixVal ZSW r2225 Tec_ctrl sel bit 2 p2222 [C] r2225 Tec_ctrl sel bit 3 p2223 [C] Tec_ctr fix val 1 -200.00 ... 200.00 [%] 0 0 0 1 p2201 [D] (10.00) Tec_ctr fix val 2 -200.00 ...
Page 632
Tec_ctr mop config p2230 [D] (0000 0100 bin) Data save active The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240. The setpoint for the motorized potentiometer is saved after OFF and after ON is entered using r2231. Without initial rounding.
Page 639
Power module Control Unit Thermal monitoring for the power module ZSW fault/alarm 2 Maximum power module temperature 1 = Fault thermal overload in power module r2135 T_max heatsink r2135 [2548.2] Temperature measurement Faults "Power unit overtemperature" F30004 Inverter heatsink F30024 Thermal model F30025 Chip F30035 Air intake PU temperatures [°C]...
Page 640
Rated motor temperature rise Calculated motor temperatures Mot temp [°C] r0035 Mot T_ambient MotTMod T_amb. [°C] -40 ... 80 [°C] r0630 [D] p0625 [D] (20) Mot T_over core MotTMod T_core [°C] 20 ... 200 [K] r0631 [D] p0626 [D] (50) Thermal 3-mass-model Mot T_over stator...
Page 641
I2t mot_mod thresh 0.0 ... 220.0 [°C] p0615 [D] (180.0) Therm Mot_mod conf - ... - p0612 [D] (0010 bin) [8016.6] Mot I_standstill 0.00 ... 10000.00 [Aeff] p0318 [D] (0.00) Thermal I_act abs val [Aeff] I²t motor model model r0068 (only for synchronous not smoothed machine)
Page 645
LED "RDY" [= red for fault] Actual fault code r2131 1 ms t_System relative 0 = "No fault present" <2> 0 ... 4294967295 [ms] p0969 (0) Fault time 32 bit counter, Fault code Fault value Fault time "removed" free running "come"...
Page 646
Actual alarm code r2132 <1> 0 = "No alarm present" Alarm time Alarm time Alarm value Alarm code "come" "removed" Operating time [8060.1] Alarm times Counter 16 bit Alarms Alarm comes Alarm 1 r2124[0] [I32] r2123[0] [ms] r2125[0] [ms] STW fault/alarm counter r2122[0] (oldest)
Page 647
Message trigger 0 ... 65535 p2128 (0) Trigger word r2129 Fault/alarm trigger word 0. Message/signal present (e.g. as trigger condition to record traces) r2129 r2129.0 0. Fault/alarm code 1. Message/signal present 1. Fault/alarm code r2129.1 15. Message/signal present [15] 15. Fault/alarm code r2129.15 Setting, fault/alarm trigger Faults and warnings...
Page 648
The fault response, acknowledge mode and message type for all faults and alarms are set to meaningful default values in the factory setting. Changes that may be required are only possible in specific value ranges specified by SIEMENS. When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
Page 660
Acknowledge: NONE Cause: At least one firmware file in the directory /SIEMENS/SINAMICS/ has been changed without authorization with respect to the version shipped from the factory. No changes are permitted in this directory. Alarm value (r2124, interpret decimal): 0: Checksum of one file is incorrect.
Page 665
16: Device status cannot be changed to "ready for operation". 18: A new download is only possible if the factory settings are restored for the drive unit. 20: The configuration is inconsistent. Additional values: only for internal Siemens troubleshooting. Remedy: - use the current version of the commissioning software.
Page 681
PROFIBUS/PROFINET cable. 6166: A time monitoring error (timeout) was identified when receiving the PROFIsafe telegram. Message values that have not been listed are only for internal Siemens troubleshooting. See also: r9725 (SI Motion, diagnostics STOP F) Remedy: Re message value = 0: - no error was identified in this monitoring channel.
Page 732
FBLOCKS: Int. meas. active Reaction: NONE Acknowledge: NONE Cause: A Siemens internal measurement has been activated. Remedy: Carry out a POWER ON (power off/on) for the Control Unit involved. F50518 FBLOCKS: Sampling time of free run-time group differs at download Reaction:...
Page 741
CU240E-2 Analog inputs as Digital inputs Status words, free interconnection, 2-538 (DI11 ... DI12), 2-510 2501 2223 Control word, sequence control, 2-540 CU240B-2 Analog inputs as Digital inputs 2503 (DI11), 2-509 Status word, sequence control, 2-541 2230 2505 CU240E-2 Digital outputs (DO0 ... DO2),...
Page 744
Display, 3-654 inputs 0 ... 1 (AI0 ... AI1), 2-514 Fault reactions, 3-656 9567 General, 3-654 CU240B-2 Analog input 0 (AI0), 2-513 How to distinguish from an alarm, 3-655 9572 Fault messages CU240E-2 Analog outputs 0 ... 1 List of all Fault messages, 3-658 (AO0 ...
Page 745
Drive Data Sets (DDS), 2-651 Handling BICO technology, 2-497 Function diagrams Faults and warnings Function diagrams Input/Output Terminals Fault buffer, 2-645 CU240B-2 Analog input 0 (AI0), 2-513 Fault/warning configuration, 2-648 CU240B-2 Analog inputs as Digital inputs Fault/warning trigger word (r2129), 2-647 (DI11), 2-509...