Siemens SIMATIC NET SCALANCE W774-1 RJ-45 Operating Instructions Manual page 10

Hide thumbs Also See for SIMATIC NET SCALANCE W774-1 RJ-45:
Table of Contents

Advertisement

Description
3.2 LED display
LED
L1
L2
PoE
P1
P2
R1
F
P1
R1
Note
Primary user (radar) on all enabled channels
If the device detects a primary user (for example radar signals) on all enabled channels of
the WLAN interface, the LED F is lit and R1 flashes. No data traffic is then possible for the
next 30 minutes. After this time, the device runs the scan again and checks whether a
primary user still exists. If no primary user is detected, data traffic is possible again.
The wait time of 30 minutes is necessary due to legal requirements and cannot be shortened
even by restarting the device.
10
Color
Meaning
Green
Power supply L1.
Green
Power supply L2.
Green
Power supply using Power over Ethernet.
Green
There is a connection via the first Ethernet interface (Link).
Green and yel-
Data transfer via the first Ethernet interface.
low flashing
alternately
Green
There is a connection via the second Ethernet interface (Link).
Green and yel-
Data transfer via the second Ethernet interface.
low flashing
alternately
SCALANCE W774 in access point mode:
Green
The WLAN interface is initialized and ready for operation.
SCALANCE W774 in client mode or SCALANCE W734:
There is a connection via the WLAN interface.
Green and yel-
Data transfer over the WLAN interface.
low flashing
alternately
SCALANCE W774 in access point mode:
Green
flashing briefly
With 802.11h, the channel is scanned for one minute for primary users
before the channel can be used for data traffic.
SCALANCE W774 in client mode or SCALANCE W734:
The client waits for the MAC address due to the setting "Automatic" for
the "MAC mode" parameter and is connected to no access point.
SCALANCE W774 in client mode or SCALANCE W734:
Green
flashing 3 x
The client waits for the MAC address due to the setting "Automatic" for
short, 1 x long
the "MAC mode" parameter and is connected to an access point.
Red
An error occurred during operation with the device.
Red
A primary user was found on all enabled channels.
R1 flashing yel-
low at the same
time
Flashing yellow
"Flashing" enabled using SIMATIC NET Primary Setup Tool (PST).
SCALANCE W774-1/W734-1
Operating Instructions, 09/2015, C79000-G8976-C325-06