Download Print this page
Hitachi RAF-35RXE Installation Manual

Hitachi RAF-35RXE Installation Manual

Floor unit air conditioner, indoor unit, hfc r32
Hide thumbs Also See for RAF-35RXE:

Advertisement

Quick Links

FOR SERVICE PERSONNEL ONLY
<0019567C>
1
EN
HITACHI FLOOR UNIT
AIR CONDITIONER
INSTALLATION MANUAL
RAF-25RXE
RAF-35RXE
Indoor Unit
RAF-50RXE
R32
SAFETY PRECAUTION
• Read the safety precautions carefully before operating the unit.
• The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION
.......... Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.
• Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
• Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause
water leakage, electric shock and fire.
• Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may
collapse and impose danger.
• Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and
fire may occur due to the use of low quality wire or improper work.
• Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fire.
• Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or
stronger vibration may occur.
• Be sure to use the specified piping set for R410A,R32. Otherwise, this may result in broken copper pipes or faults.
• When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A,R32)
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally
which could result in a rupture and injury.
• Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may
occur.
• After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
• Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
• Be sure to connect the earth line from the power supply wire to the outdoor unit and between
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the
telephone unit. Improper earthing may cause electric shocks.
• When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a
pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
• When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
The electric cables should neither be reworked nor added.
Make sure to use an exclusive circuit breaker.
Otherwise fire or electric shock might occur by connection failure, isolation failure or over current.
Make sure to connect cables to terminal properly and terminal cover should close firmly.
Otherwise, over heating at terminal contact, fire or electric shock might occur.
Make sure that there is no dust on any connected points of electric cables and fix firmly.
Otherwise, fire or electric shock might occur.
• A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the
outdoor unit. In case of other installations a main switch with a contact gap of more than 3mm has to be installed.
Without a circuit breaker, the danger of electric shock exists.
• Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire
if flammable gas leaks around it.
• Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.
• An IEC approved power cord should be used. Power cord type: NYM.
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from
customer before installation.)
WARNING
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
CAUTION
No nearby heat source and no obstruction near the air outlet
is allowed.
The clearance distances from top, right and left are specified
in figure below.
The location must be convenient for water drainage and pipe
connection with the outdoor unit.
To avoid interference from noise, please place the unit and
its remote controller at least 1m from the radio and television.
To avoid any error in signal transmission from the remote
controller, please put the controller far away from high-
frequency machines and high-power wireless systems.
[Indoor unit installation]
Direction of Piping
(For example: Wall installation)
Piping configuration may be in three
different directions: direct rear piping,
right downward piping and right
sideways piping.
Above 200mm
Be sure to completely
seal any gap with
putty.
Drain pipe
Must be installed separately.
Insulate indoor part of pipe
to prevent condensation.
< S904 :
A
>
Carefully read through the procedures of proper installation
before starting installation work.
The sales agent should inform customers regarding the
correct operation of installation.
Explanation for outdoor unit is in the "How To Use"
(Instruction Manual) that packed with outdoor unit.
Tools Needed For Installation Work
(Mark
is
excl
usive use tool for R410A,R32)
ø65mm Power
Measuring Tape
Knife
Saw
Drill
Hexagonal Wrench Key (
4mm)
( 14,17,22, 26, 27mm)
Gas leakage Detector
Cutter
Putty
Vinyl Tape
Pliers
Vacuum Pump Adapter
Manifold Valve
Hose
Vacuum Pump
WARNING
CAUTION
Names of Indoor Components
AAA size
No.
Item
Qty
Battery
6
Flare Insulator
1
1
Remote Controller
Binder
7
2
2
Insulator
Screw for Overturn
Prevention
8
8
3
(t3 × 160 × 600)
(4.1 × 32)
Screw for Overturn
Holder for Remote
Prevention
Controller
9
1
4
Insulator
Screw for holder of
Remote Controller
2
10
5
(3.1 × 16)
(20 × 30 × 300)
Bush
11
Sheet
12
Purifying Filter
13
Hanger
14
Above 150mm
14
Above 100mm
12
Sheet
When mounting on a wall
(up to 150~500 mm from the floor surface)
Bush
11
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator
(Procure locally)
7
is insufficient, please use
commercial products.)
6
1. Installation of wall penetration and installation of protection pipe
1.1
Hole position
Make a hole on the wall such the
position as shown below, in order
to keep the flow for condensed
water smooth.
Screwdriver
Wrench
Pipe
Flare Tool
Charge
1.2
Wall penetration and installation of protection pipe
Drill a ø65mm hole on wall which is slightly tilted
towards the outdoor side. Drill the wall at a small
angle.
Cut the protection pipe according to the wall
thickness.
Empty gap in the sleeve of protection pipe should be
completely sealed with putty to avoid dripping of rain
water into the room.
2. Installation of the indoor unit
2.1
How to remove the front cover
Please refer to section for details.
Removal and installation of
front cover
Screw (3 pieces)
Screw (3 pieces)
Screw (2 pieces)
2.2
Drain pipe
Make sure drain pipe slopes downward so that drain flows smoothly without being trapped in the middle.
The drain hose (connecting port outer diameter: 16mm or 20mm, length: 500mm) is included in the indoor unit. Prepare a drain
pipe as shown in the following figure.
To prevent condensation, the indoor drain pipe should be covered with heat insulation material with a thickness of more than
10mm.
After piping is completed, check to make sure that drain discharges smoothly. Seal the drain pipe tightly with tape to keep dirt out.
Front view
Drain hose
(Unit: mm)
2.3
Connecting the pipe to indoor unit
Draw in the pipes through the hole of the wall or the floor to indoor.
Arrange the pipe shown below. In the case that large pipe and small
pipe arrange to make in front and behind.
The indoor piping should be insulated with the enclosed insulation
pipe.
2
The pipe should first be cut longer than the length shown below.
The excess section of the pipe should be cut off during pipe
connection.
1
In the case of make
a hole on the floor.
Before piping.
1
above 270
40
Floor
2
Remove PIPE SUPPORT.
(4.0 × 34)
Insert the drain hose into the hole in the wall.
Winding insulation pipe for drain hose and taping 4 or 5 places to fix.
1
Connect the pipe to the Indoor unit.
After completing the piping connection, cover the connector with the insulator.
Connect the cord (follow instructions in the section "5. Connection of the connecting cord" on the reverse of this sheet).
3
3
PIPE SUPPORT
1
Since there is some space between PIPE SUPPORT and
the pipe, affix the insulator
10
As shown in the figure on the right, affix the insulator
1
to the PIPE SUPPORT to sandwich it.
After connecting the pipes and connecting cord, be sure to
screw PIPE SUPPORT tightly and fix the pipes and
connecting cord.
Position the easy-to-attach side of PIPE SUPPORT (after
aligning it with the pipe) to face the front and secure it with
a screw. (Be sure to install PIPE SUPPORT to prevent
rodents from entering the indoor unit.)
To prevent the pipe connector from contacting the front
cover, push the connector as far as it goes.
Arrange the connecting cord, pipes and drain hose neatly
and store them in the bottom section of the rear surface of
the indoor unit.
Plug
(Procure locally)
Pipe layout of the unit rear surface
Plug
4
5
Hole Position
In the case of making a hole on the wall.
In the case of making a hole on the floor.
Drain hose
make lower
than center of
the hole.
55mm
Indoor
Outdoor
Seal with
Seal with
putty
putty
Protection
pipe
Sleeve of
WALL
protection pipe
If there is a baseboard
For sideways piping
If
the
baseboard
is
For right sideways piping,
5~15mm in thickness and
cut the stand's bushing with
115mm or less in height,
a plastic cutter or similar
cut the pipe bushing to
tool and use a file for an
conform to the baseboard.
attractive finish.
Baseboard
Bushing
(2 pieces on
each side)
5
15
Make sure the drain hose
Right side view
slopes downward.
Connecting section
Drain pipe (procure locally)
88
96
For sideways piping, do not install the drain hose
sideways. Connect the drain hose so that it comes
out directly.
Sideways installation of the drain hose will prevent it
from sloping downward, causing water leakage. To
avoid dripping, make sure to pass the drain hose
under the pipe.
ke a hole on the wall.
Sideways piping.
After piping.
Top view
Small pipe
Large pipe
Wall
170
2
Binder
Wrap flare insulation,
1
Flare
bind top and bottom
insulator
flare insulation by
binder. Wrap tape on
flare insulation closely.
2
Binder
Pipe
10
Insulator
to the PIPE SUPPORT.
10
PIPE SUPPORT
Hook the PIPE
SUPPORT tab in
the square hole.
Mount PIPE SUPPORT so that the cylindrical portion of the drain
pan passes through its hole and secure it with screws located at
the right back corner.
Pipe/drain hose layout when passing through the
file in a wall
Indoor unit rear surface
Connecting cord
Connecting cord
Pipe
Pipe
8
Insulator
8
Insulator
Drain hose
65mm
CAUTION
Be sure that the wire is not in
contact with any metal in the
wall. Please use the protection
pipe as wire passing through
the hollow part of the wall so
as to prevent the possibility of
damaged by mouse.
For floor piping
For floor piping, cut the
front cover bushing with a
plastic cutter or similar
tool and use a file for an
attractive finish.
Cabinet
Cabinet
Front cover
bushing
WARNING
(Unit: mm)
Front view
Right side view
Floor
CAUTION
When mounting the flare
insulator
, make sure there is
1
a space between the insulator
and left of resin part. Otherwise,
may cause water dripping.
Screws
PIPE SUPPORT

Advertisement

loading

Summary of Contents for Hitachi RAF-35RXE

  • Page 1 In the case of making a hole on the wall. In the case of making a hole on the floor. correct operation of installation. HITACHI FLOOR UNIT water smooth. Explanation for outdoor unit is in the “How To Use” (Instruction Manual) that packed with outdoor unit.
  • Page 2 3. Fixing the indoor unit 5. Connection of the connecting cord WARNING 3.1 Floor Installation (1) Remove the cover of the electric box. Leave some space in the connecting cord for 1. Drill holes on wall. 2. Push plug into the holes. (2) Connect the connecting cords.

This manual is also suitable for:

Raf-25rxeRaf-50rxe