Mounting center feed-in joiners
9
Connection to duct
・To connect the duct with the center feed-in joiner, be sure
to align the Polarity indication(ground side) with each other.
・Only to make connection, the cover needs not to be
dismounted.
Power supply connection
・To make power supply connection, wind the power supply
cable around the terminal screw.
・To make power supply connection, connect the power supply
cable of the grounded side to the polarity side (the terminal
screw of which is plated).
Duct
Polarity indication(ground side)
Mounting Joiner L
10
Connection to duct
・To connect the duct with the joiner L, be sure to align the Polarity
indication(ground side) with each other.
・Only to make connection, the cover needs not to be dismounted.
Caution
During construction, Do not give a shock, such as 
dropping on a product, or hitting.
It may be damaged
Connect the plug of joiner and the duct linearly.
Using the single-wire cable is 1.6 mm or 2 mm.
Securely fasten the set screws and the terminal 
screws. (Proper torque: Set screw 0.98 N ・ m〜1.32 
N ・ m Terminal screw  :  1.2 N ・ m〜1.5 N ・ m )
Doing so will result in an electric shock, a fire.
The division method  look at the back of a cover 
according to a block of a circuit.
Use a triplex cable and tighten the coil to the ground 
terminal to connect one cable(Proper torque: 1.2 N ・
m〜 1.5 N ・ m).
Doing so will result in an electric shock, a fire.
Set screw
Caution
During  construction,  Do  not  give  a  shock,  such  as 
dropping on a product, or hitting.
It may be damaged.
Connect the plug of joiner and the duct linearly.
Using the single-wire cable is 1.6 mm or 2 mm.
Securely fasten the set screws. (Proper torque: 0.98 
N ・ m〜1.32 N ・ m)
Doing so may result in an electric shock or a fire.
Use a triplex cable and tighten the coil to the ground 
terminal to connect one cable(Proper torque: 1.2 N ・ m〜 
1.5 N ・ m).
Doing so will result in an electric shock, a fire.
Grund terminal(M4)
Terminal screw
(plated)
Power supply connection
・To make power supply connection, wind the power supply cable
around the terminal screw.
・To make power supply connection, connect the power supply
cable of the grounded side to the Polarity indication(ground side)
(the terminal screw of which is plated).
Set screw
Duct
Grund terminal
(M4)
Polarity indication
(ground side)
8
Duct
Polarity indication
Set screw
(ground side)
Duct
Polarity indication
(ground side)
Terminal screw
(plated)