To attach an ESD-preventive wrist strap:
Wear the wrist strap on your wrist.
1.
Lock the wrist strap tight around your wrist to keep good contact with the skin.
2.
Insert the ESD-preventive plug into the ESD-preventive socket.
3.
Connect the alligator clip to the rack.
4.

EMI

All electromagnetic interference (EMI) sources, from outside or inside of the router and application system,
adversely affect the router in a conduction pattern of capacitance coupling, inductance coupling,
electromagnetic wave radiation, or common impedance (including grounding system) coupling. To
prevent EMI, follow these guidelines:
Take measures against interference from the power grid.
Do not use the router together with the grounding equipment or lightning-prevention equipment of
power equipment, and keep the router far away from them.
Keep the router far away from high-power radio launchers, radars, and equipment with high
frequency or high current.
Use electromagnetic shielding when necessary.

Lightning protection

To better protect the MSR4000 router from lightning, do as follows:
Make sure the grounding cable of the chassis is well grounded.
Make sure the grounding terminal of the AC power receptacle is well grounded.
Install a lightning arrester at the input end of the power supply to enhance the lightning protection
capability of the power supply.
Install a special lightning arrester at the input end of outdoor signal lines (for example, E1/T1 line)
to which interface modules of the router are connected to enhance the lightning protection
capability.

Rack-mounting

Before mounting the router in a standard 19-inch rack, adhere to the following requirements:
The rack is equipped with a good ventilation system.
The rack is sturdy enough to support the router and its accessories.
For heat dissipation and device maintenance, make sure the front and rear of the rack are at least
0.8 m (2.62 ft) away from walls or other devices, and the headroom in the equipment room is no
less than 3 m (9.84 ft).

User-supplied installation tools

Phillips screwdriver: P1- 1 00 mm (3.94 in), P2- 1 50 mm (5.91 in), and P3-250 mm (9.84 in)
Flat-blade screwdriver: P4-75 mm (2.95 in)
Various types of screws
Meters and devices, including hub, configuration terminal, optional modules, and multimeter