AT C U R R E N T I N S T R U M E N T T R A N S F O R M E R
4
I N S T R U C T I O N S F O R I N S TA L L AT I O N , U S E A N D M A I N T E N A N C E
2.
02 AT35/41 mouting
points
03 AT38 mounting
3.
points
4.
Mounting
Mounting points are showed on picture below
Mounting points
02
Mounting points
03
The AT transformer is mounted in different
ways-using rings to fix the transformer directly to
the bushing, using flanges, or other ways of fixa-
tion. The mounting is not a part of transformer
delivery and the customer is fully responsible for
installation in the right way.
Ground always the metallic base of the
instrument transformer.
Connect always one terminal of each sec-
ondary winding of the transformer to the
earth. When the secondary of trans-
former is interconnected, there should
be only one grounded point to prevent
accidental paralleling with system
grounding wire.
Always short-circuit the secondary of the
current transformer, which is not cur-
rently in use, to prevent secondary volt-
ages, which may be hazardous to per-
sonnel or damaging to the transformer's
secondary. The secondary like this must
be additionally grounded.
Tightening torques
AT35 (M12)
AT38 (M16)
AT41 (M16)
The producer has not any liability for incorrect
mounted form or possible consequences of it.
Nuts and threaded rots are delivered on cus-
tomer request.
Connection of transformer primary side
The AT transformers don´t have its own primary
conductor. The primary conductor is designed as
a bushing with its own insulation, or insulated ca-
ble.
Connection of the transformer secondary side
Secondary outlets are marked by color. Which
color is assigned to which wire you can see in ta-
ble below.
Outlets marking
Lifting points
test wire (measure side)
test wire (earth side)
screen earth
secondary wire xS1
(X1, Y1, Z1, U1, V1, W1)
secondary wire xS2
(X2, Y2, Z2, U2, V2, W2)
secondary wire xS3
(X3, Y3, Z3, U3, V3, W3)
secondary wire xS4
(X4, Y4, Z4, U4, V4, W4)
secondary wire xS5
(X5, Y5, Z5, U5, V5, W5)
secondary wire xS6
(X6, Y6, Z6, U6, V6, W6)
4. Instructions for use
Current instrument transformers are used:
• to convert large currents in the primary circuit
to an appropriate level for secondary circuit
equipment (relays and meters);
• to insulate primary and secondary circuit from
each other to protect the secondary equipment
from the harmful effects of large current ap-
pearing during the operation (short circuits).
30 Nm
30 Nm
50 Nm
black marked with M
black mark with Ground
black mark with Ground
black and marked with core/
terminal no.
red and marked with core/
terminal no.
yellow and marked with core/
terminal no.
blue and marked with core/
terminal no.
grey and marked with core/
terminal no.
brown and marked with core/
terminal no.