M4M 30 NETWORK ANALYZER USER MANUAL

3.5.Technical data

Auxiliary power supply
Voltage range
Frequency
Power Consumption
Installation category
Protection fuse
Measurement accuracy*
Measurement type
IEC 61557-12
Active energy
Reactive energy
Active power
Reactive power
Apparent power
Voltage
Current
Neutral current
Frequency
Unbalances
Harmonics, THD (Current, voltage)
*Accuracy referred to insertion with .../5A CT or Rogowski coils. Derating for .../1A CT.
Voltage measurement inputs
Measurement range
Measurement category
Rated frequency
Max. VT secondary (indirect connection)
Max over voltage
Protection fuse
Current measurement inputs
Number of current inputs
Indirect insertion with CT
CT secondary
Measurement range without accuracy derating
Starting current
Burden
Indirect insertion with Rogowski coils
Rated current
Measurement range without accuracy derating
Starting current
[V]
48 to 240 VAC/VDC ±15%
[Hz]
50/60 Hz ±5%
[VA]
10 VA max
CAT III 300V class per IEC 61010-1 edition 3
T1 A - 277 VAC
True RMS up to the 40th harmonic
128 samples per cycle, zero blind
IEC 61557-12 PMD/S/K70/0,5
Class 0,5 acc. to IEC 61557-12
Class 0,5S acc. to IEC 62053-22
Class 2 acc. to IEC 61557-12
Class 2S acc. to IEC 62053-23
Class 0,5 acc. to IEC 61557-12
Class 1 acc. to IEC 61557-12
Class 0,5 acc. to IEC 61557-12
Class 0,2 acc. to IEC 61557-12
Class 0,2 acc. to IEC 61557-12
Class 0,2 acc. to IEC 61557-12
Class 0,1 acc. to IEC 61557-12
Class 0,2 acc. to IEC 61557-12
Class 1 acc. to IEC 61557-12
[V]
50 - 400 VAC (L-N) 87 - 690 VAC (L-L)
400V~ (CAT III)
[Hz]
50-60 Hz
[V]
400 VAC (L-N)
[V]
800 VAC (L-L)
T1 A - 277 VAC
4 (L1, L2, L3, N)
5 A (Class 0.5S)
1 A (Class 1)
50 mA - 6 A
5 mA
0.024 VA at 6 A
(only M4M 30 Rogowski)
10000 A
100 A - 12 kA
10 A