Selecting the IED blocked or IED test and blocked mode

The IED blocked mode and the IED test and blocked mode can be activated by from
the IED test view. The test mode can be used for simulated testing of functions and
outputs without providing current inputs. The IED blocked mode can be used to
block the physical outputs to the process.
1.
2.
3.
4.
3.6

ABB Product Data Registration

The ABB Product Data Registration feature traces composition changes in the IED's
SW or HW. Traceability allows better support and maintenance possibilities.
After a composition change, an LCT indication is seen on the WHMI at the IED
startup. The PCM600 reads the changed data from the IED. Therefore a connection
to the IED must be established first. Composition data can be read with PCM600 by
enabling LCT during PCM600 installation and activating collection in PCM600 from
'Lifecycle Handling' menu. For detailed information see PCM600 online help.
The number of composition changes can be seen from the Composition changes
parameter in Main Menu > Monitoring > IED status.
SSC600
Operation Manual
Select IED test from the main menu structure to activate the IED test view.
Figure 6: IED test view
Enable parameter editing by selecting Enable Write
Select the IED blocked mode and the IED test and blocked mode by changing
the New Value field selection.
Select Write to IED
The selected test mode is now activated.
If the IED blocked or IED test and blocked mode is not cancelled, it
remains on and the Start and/or Ready LEDs remain flashing.
to save changes into the IED's memory.
Commissioning
.
29