Troubleshooting
Different actions are taken depending on the severity of the fault. The IED tries to
eliminate the fault by restarting. After the fault is found to be permanent, the IED
stays in the internal fault mode. All other output contacts are released and locked
for the internal fault. The IED continues to perform internal tests during the fault
situation.
The internal fault code indicates the type of internal IED fault. When a fault appears,
the code must be recorded so that it can be reported to ABB customer service.
Fault indication
Internal Fault System error
Internal Fault File system er-
ror
Internal Fault Test
Internal Fault
SW watchdog error
Internal Fault License check
fail
5.3.2

Warnings

Warnings are shown in the event list of the WHMI. The text Warning additionally
provided with the name of the warning, a numeric code as well as the date and time
is shown on the WHMI. The warning indication message can be manually cleared.
Table 12: Warning indications and codes
Warning indication
Warning IEC61850 error
Warning Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning Logic error
Warning
SMT logic error
Table continues on the next page
58
Fault code
2
7
8
10
117
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Warning code
20
24
25
26
27
28
29
1MRS758850 C
Additional information
An internal system error has
occurred.
A file system error has occur-
red.
Internal fault test activated
manually by the user.
Watchdog reset has occurred
too many times within an
hour.
The devices is equipped with
invalid license.
Additional information
Error when building the IEC
61850 data model.
Error in the Data set(s).
Error in the Report control
block(s).
Error in the GOOSE control
block(s).
Error in the SCL configuration
file or the file is missing.
Too many connections in the
configuration.
Error in the SMT connections.
SSC600
Operation Manual