Setting Passwords; Identifying Ied Application Problems - ABB SSC600 Operation Manual

Smart substation control and protection for electrical systems
Hide thumbs Also See for SSC600:
Table of Contents

Advertisement

1MRS758850 C
5.4.3

Setting passwords

User password can be set via the WHMI or with PCM600.
1.
2.
3.
4.
5.4.4

Identifying IED application problems

• Check that the function is on.
• Check the blocking.
• Check the mode.
• Check the measurement value.
• Check the connection to trip and disturbance recorder functions.
• Check the channel settings.
5.4.4.1
Checking of the power supply
Check that the auxiliary supply voltage remains within the permissible input voltage
range under all operating conditions. Check that the polarity is correct before
powering the IED.
5.4.4.2
Sample data interruptions
Occasionally IEDs can receive corrupted or faulty measurement data during
runtime. In these cases the operation system halts the corresponding application
execution until correct data is received. In case of permanent faults, the
measurement chain should be checked to remove the origin of the faulty
measurement data.
SSC600
Operation Manual
Select Configuration > Authorization > Passwords from the main menu
structure.
Enable parameter editing by selecting Enable Write
Set the new password in the respective New Value field.
Select Write to IED
If the password of the last user with User Management right (refer to
table Default roles-to-rights in the Cyber Security Deployment Guideline)
is lost, contact ABB technical customer support.
In case of persistent faults originating from IED's internal faults, contact
ABB for repair or replacement actions.
to save changes into the IED's memory.
Troubleshooting
.
61