Functions
3.8 Switch onto Fault Protection (50LC/SOTF)
second harmonic current content by the 81HBL2 element. This parameter can be configured to inhibit the
overcurrent element automatically by configuration of this setting.
Parameter State
Off
Inhibit
Settings Menu
CONFIGURATION > FUNCTION CONFIG
Parameter
Gn 50LC/SOTF
CONFIGURATION > CURRENT PROTECTION > 50LC/SOTF
Parameter
Gn 50LC Setting
Gn 50LC Inrush
Action
Information List
Input/Output Matrix User Logic
Inhibit 50LC
50LC
70
Description
The element is not inhibited by operation of the 81HBL2 element
The overcurrent element is inhibited by operation of the 81HBL2 element and
automatically released when the 81HBL2 element resets.
Setting Options
Disabled
Enabled
Setting Options
1 to 20 ⋅ I
rated
Δ 1 ⋅ I
rated
Off
Inhibit
Type
Inhibit 50LC
Input
50LC
Output
Settings
Default
Gn1
Disabled
Settings
Default
Gn1
2 ⋅ I
rated
Off
IEC 103
C53000-G7040-C101-2, Edition 09.2020
Gn2
Gn2
Modbus RTU