Figure 1.2 Single Line Diagram-Bypass Operation; Figure 1.3 Single Line Diagram-Battery Operation - Mitsubishi Electric 9700 Series Owner Technical Manual

Uninterruptible power supply system
Hide thumbs Also See for 9700 Series:
Table of Contents

Advertisement

Get user manuals:
See SafeManuals.com
MITSUBISHI
ELECTRIC
OWNERS / TECHNICAL MANUAL
B) Internal Static Bypass Line (FIGURE 1.2)
The Internal Static Bypass line is a Hard wired line through CB3, contactor 52S which
supplies the critical load with unconditioned input power. The purpose of this line is to
route power to the critical load while the UPS module is de-energized during Start-up
before the system is fully operational.
FIGURE 1.2 Single Line Diagram- Bypass Operation
CB
AC Bypass
Input
Use supplied
MCCB
AC input
CB1
C) Inverter supply at battery operation (FIGURE 1.3)
FIGURE 1.3 Single Line Diagram - Battery Operation
CB
AC Bypass
Input
Use supplied
MCCB
AC input
CB1
If the input power is interrupted, the battery will immediately supply the DC power required
by the Inverter to maintain continuous AC power to the load. A fully charged battery will
provide power for the specified time at the rated load, or longer, at a reduced load.
MITSUBISHI ELECTRIC 9700 SERIES UPS
9700 SERIES UPS
CB3
CONVERTER
INVERTER
CB2
Battery cabinet
CB3
CONVERTER
INVERTER
CB2
Battery cabinet
Page Number:
1-4
Static Transfer
Switch
52S
Output
52C
Power Flow
Not in Use
UPS Module
Static Transfer
Switch
52S
Output
52C
Power Flow
Not in Use