Referring to Figures 3.2-a~h, connect UPS load terminals A50, B50, C50 and N50 to
load distribution panel. Refer to Table 3.4 for cable sizes.
H)
Connect external signal terminal block as needed. Refer to section 2.4 and Figure
2.15 for functional description.
recommended.
1. Confirm that all UPS internal contactors(breakers) "CB1", "CB2", and
NOTES:
"CB3" are open before energizing UPS.
UPS power terminals are supplied with bus bar and hardware (12mm
2.
diameter Nut/Bolt assembly). It is recommended that compression lugs be
used to fasten all input/output power cables.
recommended compression lugs and appropriate crimping tool.
If three wire source for input and bypass input is utilized, the neutral
3.
conductor is the UPS must be banded to ground.
MITSUBISHI ELECTRIC 9700 SERIES UPS
9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
12 AWG, or less, shielded conductor is
Page Number:
3-4
Refer to Table 3.5 for