Since fault current owing through the conductors causes large electromagnetic forces, the conductors should be
secured rmly, using the values in the below table as a reference. Max. distance between xing support and breaker
bus bar should be less than 200mm.
Conductor
Breaker
200 mm or less
Supporting xture
Supporting between live parts of
different poles and between the
power supply and load terminals.
Fig. 11-1
When selecting conductors to be connected to the breakers, ensure that they have a suf cient current capacity. Refer to the right table.
Table 11-2
Conductor size
(IEC 60947-1, Ambient Temp. 40 °C, Open air)
Conductor to be connected (copper)
Rated current
MAX (A)
Quantity
Conductor size (mm)
2
40 x 5
630
2
60 x 5
1000
2
80 x 5
1250
2
100 x 5
1600
3
100 x 5
2000
4
100 x 5
2500
3
100 x 10
3200*
1
2
150 x 10
4000
4
150 x 10
AE4000-SWA
drawout type
4000
AE4000-SWA
150 x 10
3
xed type
4000
4
100 x 10
(AE4000-SW)
5000
4
150 x 10
6300
4
200 x 10
*1 For 3200 A, connect a conductor which is sized for 3150 A.
For 3200 A or higher, there is no speci cation by IEC (IEC 60947-1). (Speci cation by the manufacturer)
Control circuit terminal block
Tighteing with excessive torque above the specification may cause damages of
terminals and screws.
Be sure to tighten with the specified torque.
After removing screws, make sure not to tighten the screws diagonally.
Be careful not to apply excessive tension to the wirings.
Use a cross-head screwdriver with a diameter that matches the cross-shaped
groove.
M3.5 ................................. No. 2
Control circuit terminal block
Applicable crimp-type terminals
Applicable crimp-type terminals
for M3.5 screws with an outer
diameter of 7.2 mm or less.
(Wire size 1.25 mm
A
A
A = 7.2 mm or less
Fig. 11-3
Table 11-1
Electromagnetic force per 1 m of conductor (in the case of three phase short circuit)
AE630-SW ~
Type
AE1600-SW
3 poles
Conductor distance (mm)
85
Prospective fault current kA (pf)
30(0.2)
7700
42(0.2)
15100
50(0.2)
21400
65(0.2)
36100
75(0.2)
-
85(0.2)
-
100(0.2)
-
130(0.2)
-
Arrangement
(Note) Table 11-2 shows the conductor size that is indicated in IEC 60947-1
with an ambient temperature of 40 °C and in an open air environment.
Fig. 11-2 shows the testing conditions.
Vertical
~ 2.0 mm
)
2
2
AE2000-SWA
AE2000-SW ~
Drawout type
AE3200-SW
4 poles
3 poles
115
105
130
190
5700
6300
5100
3500
11200
12200
9900
6800
15800
17300
14000
9600
26700
29300
23600
16200
-
-
31500
21500
-
-
40400
27600
-
-
-
-
-
-
-
-
3m
Breaker
2m
Fig. 11-2
Crossover wiring
M3.5 x 10
Torque: 1.0 ± 0.2N·m
Fig. 11-4
(N/m)
AE4000-SWA
AE4000-SW ~
Fixed type
AE6300-SW
4 poles
3 poles
4 poles
170
152
145
262
3900
4300
4500
2500
7600
8500
8900
5000
10700
12000
12600
7000
20200
21200
18100
11800
24100
26900
28200
15800
30900
34500
36200
20000
-
-
-
27800
-
-
-
47000
Fig. 11-5
E-11