⑤ When the breaker is drawn out to the TEST position,
the drawout position indicator shows TEST position,
and the lock plate is protruded automatically, locking
the drawout handle rotation.
(Caution)
Do not rotate the drawout handle while the lock
plate is protruded.
⑥ Next, insert the locking plate and rotate the handle
counterclockwise until the drawout position indicator
shows DISCONNECT and the breaker does not move.
Drawout operation is now completed.
The breaker can be pulled out using both hands.
(Caution)
(a) The lock plate sometimes gets protruded before
reaching the DISCONNECT position. If that is the
case, push in the lock plate to stay in the unlocked
state, and continue rotating the handle.
(b) If unlocking the lock plate feels difficult, slightly
rotate the drawout handles to the right and left.
(c) At the DISCONNECT position the drawout handle
may spin around without the lock plate being
protruded.
To detach the breaker from the cradle, pull the lock lever
toward you, unhook, pull out the extension rail evenly on
the right and left side, and then pull out the breaker.
CAUTION
Drop
By pulling the breaker, the
center of gravity shifts forward.
Be sure to take preventative
measures against a fall or drop
when the cradle is not secured.
Fig. 15-3
CAUTION
Pinched finger
When pulling out the breaker,
take care not to hurt your fin-
gers or hands with the in-panel
structure.
Automatic
TEST position
Fig. 15-1
DISCONNECT
position
Fig. 15-2
Fig. 15-4
Lock lever
E-15