LG Becon PREMTA000 Engineering Product Data Book page 14

Individual controller

Advertisement

HVAC Solution
TM
2.1 Product Feature
Category
Level1
Mode setting
External
equipment
control
User setting
Wi-Fi
Wi-Fi pairing
Zone Control
(damper control)
Function setting
Zone /
Damper Control
Installer setting
Mode setting
2 set
control
Function setting
Home leave set temperature
Expand of temperature range
Installer setting
Level2 (Code)
Level3 (Code)
-
On/Off/Auto
External device use
Not use / Use
Motor/Lighting/
External device type
Fan/Heater/
Pump/Others
On condition
-
Off condition
-
-
-
-
-
Zone Name
-
V-H (06:01)
Static pressure
F-H (06:02)
code : 06
V-L (06:03)
F-L (06:04)
Old (default)
(13:00)
New (4 zone)
Zone Type
(13:01)
code : 13
New (8 zone)
(13:02)
2~4 for New 4 zone
(14:02~14:04)
Zone number
code : 14
2~8 for New 8 zone
Step 0 :
Not use (32:00)
Static pressure step
Step 1~11
(32:01~32:11)
Auto (dual set point)
-
-
Override
Home Leave(Setback)
-
Hold
-
-
Temporary
Dead band setting
0 ~10℉(0~5℃)
Override set time
30~240 minutes
Cool/Heat
Clear (31:00)
code : 31
Set (31:01)
0 minute (33:00)
15 minutes (33:01)
Guard timer
30 minutes (33:02)
code : 33
45 minutes (33:03)
60 minutes (33:04)
DESCRIPTION
You can control external devices such as lights, fans, and heaters by using the signals
emitted by the remote controller.
- Output specification : DC 11~12 V , Max 30 mA
On : When it is set to "On", it always performs the contact point output
Off : When you set it to "Off", it does not perform the contact point output in any case.
Auto : If it is set to "Auto", a contact signal comes out according to the condition set in the
on/off condition of the user setting.
The external device is turned on by the set mode or temperature condition.
The external device is turned off by the set mode or temperature condition.
Enables the AP mode function of the Wi-Fi module connected to the indoor unit.
You can monitor or set the status of zone.
If the zone control of the indoor unit is "New type", You can set the zone name.
- Zone(default)/Office/Hallway/Lobby/Room/Living/Kitchen/Etc.
This function can be set only in the duct products.
When using zone control, this is a function to change the fan air volume according to the
number of damper opening and closing and the static pressure of the indoor fan.
V-H : Variable - High static pressure
F-H : Fixed - High static pressure
V-L : Variable - Low static pressure
F-L : Fixed - Low static pressure
This function sets the Zone type supported by indoor units such as "New" and "Old" type.
1) Old (default) - Only the condition of damper can be monitored.
2) New (4 zone) - 4 zone damper controller is installed. Both damper control and monitoring
are possible.
3) New (8 zone) - 8 zone damper controller is installed.
Both damper control and monitoring are possible.
If zone control of indoor unit is "New type", set the number of installed zone damper.
Static pressure step setting can be set only for duct products.
This function can set the static pressure of the product in 11 steps.
If Static pressure step setting(code:32) is used, the Static pressure(code:06) can not be
used.
The cooling and heating are automatically switched and operated through the desired tem-
perature setting for heating and cooling.
It is a function to switch temporarily the status of the occupied/unoccupied of the set sched-
ule. (occupied ↔ unoccupied)
When using the home leave mode(setback), the room temperature can be maintained at
the temperature set by the user.
Set the desired temperature in "Function Settings-Home leave set temperature".
The home leave mode is canceled when this mode is released directly or when the occu-
pied schedule starts.
This function maintains the current operation status without executing schedule.
It can be released only by releasing the hold function.
It is a function that operates differently from the scheduled schedule by user's arbitrary
operation or external setting.
When the schedule event time is reached, the schedule operation is performed and the
temporary mode is released.
It is the function to set the difference value of minimum interval between cooling desired
temperature and desired heating temperature.
In case of occupied/unoccupied switching, the product operation is maintained in the
changed mode for the set time.
Set the desired cooling and heating temperature when the home leave mode is executed.
This function using in dual set point control mode.
This function is used to expand of temperature range.
Clear: 60~86°F (16~30°C) (Default)
Set : 40~99°F (4~37.5°C)
This is the function to set the minimum waiting time for cooling / heating switching during
dual set mode operation.
It protects the outdoor unit by setting the waiting time when changing the outdoor unit cycle.
-
-
Wired remote controller