SVR Service Control Package
Instruction Manual
6F8C0909

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba TOSDIC-CIE DS

  • Page 1 SVR Service Control Package Instruction Manual 6F8C0909...
  • Page 2 Edition 25 May, 2018 The contents of this manual may be revised without notice.  Copy right 2018 TOSHIBA INFRASTRUCTURE SYSTEMS & SOLUTIONS Corporation. All rights reserved. No part of this manual may be reproduced in any form without permission.
  • Page 3: Safety Precautions

    Safety Precautions Safety Precautions The instruction manual and the labels affixed to the products or equipment give important information for using products safely. It helps prevent damage to properties and hazard to people who use them or work with them. Make yourself familiar with the signal words and signs in this page, then read the safety precautions that follow and always follow the instructions to avoid hazards.
  • Page 4 Safety Precautions Caution • Do not shut off power, or insert or extract connectors while the system is operating or data is being written.  This can cause an erroneous system operation or damage to data. Power shutdown prohibited while system is operating •...
  • Page 5 • To use this product in a system where equipment such as the one human safety is involved and affecting the maintenance of public function(Note 2), special consideration (Note 3) regarding the system’s operation, maintenance and control is required. Contact Toshiba’s sales department. Note 1 Example of equipment directly involved in human life is as follows: ...
  • Page 6  Toshiba is not liable for any incidental damage from use or non use of this product (loss of business profit, discontinuation of business, change or loss of the memorized content and so on).
  • Page 7: Introduction

    This manual describes mainly how to use and operate the SVR Service Control Package, which is used to build OIS(SVR) (OIS with server functions) of TOSDIC-CIE DS. To understand the functions of the SVR Service Control Package, read this manual thoroughly before you use the system.
  • Page 8 Introduction  Related Manuals For more information on setup, refer to the following manuals. • OIS-DS53, OIS-DS63, OIS-DS/SMART, SVR-DS63 Windows 7 Version Installation Manual (6F8C1442) • OIS-DS53, OIS-DS63, OIS-DS/SMART, SVR-DS63 Windows 10 Version Installation Manual (6F8C1636) For more information on the common functions of OIS, refer to the following manuals. •...
  • Page 9: Table Of Contents

    Contents Contents Safety Precautions Introduction 1. SVR Service Control Package Overview ············································· 1 Basic Specifications ······················································································ 1 Configuration ······························································································· 4 2. Functions ······················································································ 9 Historical Database ······················································································· 9 Tag Functions ······························································································ 20 Monitoring Functions ····················································································· 21 Redundancy Control ······················································································ 24 Station Timer Synchronization ·········································································...
  • Page 10 Contents...
  • Page 11: Svr Service Control Package Overview

    The SVR Service Control Package adds to OIS-DS the functions equivalent to those of SVR-DS to make it as OIS(SVR) (OIS with server functions). OIS(SVR) allows you to build a TOSDIC-CIE DS system without SVR-DS. The SVR Service Control adds the following functions to OIS-DS.
  • Page 12 1. SVR Service Control Package Overview Table 1.1 Station Configuration of the TOSDIC-CIE DS System Control LAN 10M Ethernet Control LAN 100M Ethernet Station Type Configuration Configuration OIS(SVR) 1 unit or a set of redundant units 1 unit or a set of redundant units...
  • Page 13 1. SVR Service Control Package Overview Table 1.2 Comparison of OIS(SVR) Basic Specifications (2 of 2) Item Specifications Alarm Monitor On/Off Process alarm: by tag, individual alarm Process alarm: by tag, individual alarm Signal Categories 64 signal categories 64 signal categories Label Select from 32 labels or Edit directly Select from 32 labels or Edit directly...
  • Page 14: Configuration

    1. SVR Service Control Package Overview Configuration Functions Overview The SVR Service Control Package implements the functions equivalent to those of SVR-DS on OIS-DS. Figures 1.3 and 1.4 show the function configurations of OIS/SVR. OIS-DS OIS Standard Software Standard Screen Graphics Peripheral Device Background...
  • Page 15 1. SVR Service Control Package Overview OIS(SVR) OIS Standard Software Standard Screen Graphics Peripheral Device Background Control Ethernet Communication SVR Service Control Package Database Functions Historical Database Report Database History Save Tag Functions OIS Parameters Internal Tags Guidance Monitor Functions Event Conditions Redundancy Control External Alarm...
  • Page 16 The redundancy control function monitors the another redundant station to control the online/standby state. (5) Station Timer Synchronization Monitors and corrects the timer of the TOSDIC-CIE DS system. Software Configuration Install the SVR Service Control Package software with the OIS Standard software.
  • Page 17 1. SVR Service Control Package Overview Table 1.3 OIS(SVR) Standard Software (with SVR Functions) Software Name Type OIS Graphic Engine Package ECPGMSDB ECPGMSDD OIS Window ECHIWDDD OIS Service Control ECHISCDD Standard Graphic Models ECHIGMDD Sentinel Driver ECHISDDB PCMP Support Software EPPCMPSA LAN Management Software ECHILADA...
  • Page 18 1. SVR Service Control Package Overview...
  • Page 19: Functions

    2. Functions 2. Functions Historical Database The Historical Database is on the OIS(SVR) hard disk. It collects and saves historical trend data, history messages, report data, and data of user applications running on the ONS station by historical tag. These types of data are read out by OIS-DS and OIS(SVR). Historical Tag Registration Screen Display Report...
  • Page 20 2. Functions Table 2.1 Specifications of Historical Database Item Specification Data Collected Controller/AEGW/PLCS process tags SVR internal tags Application set values Parameter tags Collection Cycle Fixed-Cycle Trend data: 15 types, 5 sec to 1 day Collection Report data: 1 minute Event On/Off of collection based on event conditions...
  • Page 21 2. Functions OIS(SVR) Report Window (Excel) Save Printing Maintenance External Function Function Storage Report Interface Read Change Report Database Report Tag Hour Month Year Data Data Data Data Report Calculation Process 1-minute cycle data → Hour → Day → Month → Year Historical Database Historical Tag Data Collection Process...
  • Page 22 2. Functions The specifications of report data are as follows. Table 2.2 Specifications of Report Database Item Specification Data Collected Controller/AEGW/PLCS process tags SVR process internal tags Operator set values parameter tags Collection Synchronization 1 minute Collected Items Up to 2500 tags/system. Total with historical tags.
  • Page 23 2. Functions (2) Hour-Maximum mode Calculates the day-maximum value, day-maximum value time, day-minimum value, day-minimum value time, and day-mean value for one day (24 samples) of Hour data, and saves the result in the report tag as Day data. (3) Hour-Mean mode Calculates the day-maximum value, day-maximum value time, day-minimum value, day-minimum value time, and day-mean value for one day (24 samples) of Hour data, and saves the result in the report tag as Day data.
  • Page 24 2. Functions month-maximum value, month-minimum value, and month-mean value of Month data, and saves the result in the report tag as Year data. (3) Hour-Mean mode Calculates the year-maximum value, year-maximum value time, year-minimum value, year-minimum value time, and year-mean value for one year (12 samples) of the month-mean value of Month data, and saves the result in the report tag as Year data.
  • Page 25 2. Functions Minute Mode Day Data Month Data Year Data January Year 31st December Maximum Maximum Maximum Value Value Value Minimum Minimum Minimum Value Value Value Average Average Average Value Value Value Hour-Maximum Mode Minute Data Hour Data Day Data Month Data Year Data 00:01...
  • Page 26 2. Functions Report data processing of Power Factor Indicator tags The Power Factor Indicator tags of process tags of Controller/AEGW/PLCS calculate the maximum, minimum, and mean values in the following report calculations. For the maximum and minimum values, either one of the phase specification calculation or absolute value calculation mode is selected.
  • Page 27 2. Functions 1) Counter Calculates the difference between the nth data and (n-1)th data of the historical tag data collected in one minute cycles, and sums the results. 2) Analog totalization Converts the historical tag data collected in one minute cycles by using the time conversion coefficient registered to the historical tag, and sums the results.
  • Page 28 2. Functions Missing values For Hour, Day, Month, and Year data, missing values occur in the following situations. (1) Hour data For report calculation of Hour data, Hour data becomes a "missing value" when all data of the historical tag data collected in one minute cycles in one hour is invalid. Historical tag data is invalid when;...
  • Page 29 2. Functions History Save OIS(SVR) monitors the processes and systems and saves the record message history such as the process and system alarms occurred, guidance, operations of digital tags, operations of the operators. Up to 32000 histories can be saved for one system on the OIS(SVR) hard disk (Historical Database).
  • Page 30: Tag Functions

    2. Functions Tag Functions OIS Parameters Control the parameters of OIS. The tag types of OIS parameters are as follows. • 1-byte signed integer (char) • 1-byte unsigned integer (unsigned char) • 2-byte signed integer (short) • 2-byte unsigned integer (unsigned short) •...
  • Page 31: Monitoring Functions

    2. Functions System Tags Monitor self OIS-DS system. In OIS-DS, system tags provide access support to the system and notify of status changes for alarm control. Monitoring Functions Event Conditions OIS(SVR) controls the event conditions used to trigger guidance or history message printing, and the bit data indicating occurrence/recovery of events.
  • Page 32 2. Functions Up to eight event condition elements for an event condition. You can specify whether to inverse logically the results of the operation. The following items can be specified for each event condition element. • Tag number • Atom name Bits of an alarm state, on/off of Tag Representative Alarm Monitoring, •...
  • Page 33 2. Functions Switches to the alternative printer when the destination printer fails. 2) Filtering function You can specify event conditions that prohibit message printing for the related events when tag event conditions such as process alarm, system alarm, or guidance are met to suppress message printing.
  • Page 34: Redundancy Control

    2. Functions Redundancy Control For redundant OIS(SVR), online/standby is switched when the online OIS(SVR) goes down. Switching is performed when; 1) online/Stand-by is switched manually. 2) operation of the online OIS(SVR) stops, or 3) an error occurs in the online OIS(SVR), which becomes a stand-by OIS(SVR). Table 2.3 shows the redundant functions in the redundant system.
  • Page 35: Station Timer Synchronization

    OIS(SVR) monitors the timers of OIS-DS and Controllers/AEGW/PLCS connected to the Ethernet control LAN of the TOSDIC-CIE DS system at regular intervals (in about 5-minumte cycles). When the allowable time difference (within 5 seconds) is exceeded, the timer is set to the system timer of the self OIS(SVR).
  • Page 36 2. Functions Expands when the redundancy partner is displayed and selected only for redundancy registration OISX Redundant Primary OIS 4 (SVR) Station Status : OIS 3 (SVR) CPU load 1-32 Memory space Disk space 32-64 Prev down info Redundant Current time status is displayed only Dual oparate...
  • Page 37: Engineering

    3. Engineering 3. Engineering Monitoring Functions Station Configuration When you register OIS(SVR) for station configuration, the following screen is displayed. Figure 3.1 The Station Configuration Setup Screen Table 3.1 Station Configuration Setup OIS-DS SVR-DS OIS(SVR) Station Name Arbitrary name Arbitrary name Arbitrary name Redundancy Form Single...
  • Page 38 3. Engineering Peripheral Device Configuration The peripheral device configuration of OIS(SVR) is registered in "Peri. Device Config(OIS)". If the Node Type is "OIS??(SVR)" in station configuration, the station name registered in the "OIS Station Name" field is displayed. The same items are registered as OIS-DS. Whether each peripheral device exists or not is specified.
  • Page 39 3. Engineering Buzzer Output If the Node Type is "OIS??(SVR)" in station configuration, the station name registered in the "OIS Station Name" field is displayed. The same items are registered as OIS-DS. Specify each item. Figure 3.3 The Buzzer (DIO) Screen...
  • Page 40: Trend Function

    3. Engineering Trend Function Trend Tag Up to 2500 points of historical tags can be registered in OIS(SVR). Figure 3.4 The Historical Tag in OIS-DS engineering Tool You don't need to specify the Storage Node. When you save Archive data using SVR-DS, set an archive group No. and register the Archive Group.
  • Page 41 3. Engineering Archive Group Up to 16 groups of archive groups can be registered. Archive Manager read this register, and save archive data in “Storage destination” periodically. Table 3.2 Archive Group Information Item Brief description Backup Cycle Set a backup cycle. When it is “None”, Archive Manager function is invalid. Storage Start Date Set a storage start date(Year/ Month/ Day/ Hour/ Minute).
  • Page 43 Industrial Systems Division 72-34, Horikawa-Cho, Saiwai-Ku, Kawasaki 212-8585, Japan...