Troubleshooting
Appendix A – Troubleshooting
If the following troubleshooting solutions do not resolve the
problem, or you experience a problem not covered in this
section, contact an authorized Toro distributor for assistance.
The power indicator light does not illuminate when the
On/Off switch is in the On position.
• Ensure the power supply is plugged into an outlet and the
outlet has power.
• Ensure the power supply cord is plugged firmly into the
TouchNet receptacle.
• Check for 11 to 14 VDC on the orange power connector.
• Ensure the polarity is correct - plus to plus terminal and
minus to minus terminal.
No display appears on the screen.
• Ensure the power indicator light is on and the On/Off switch
is in the On position.
• If the power indicator light does not come on, refer to the
solutions above.
• If the power indicator light is on, touch any part of the
display screen. The TouchNet screen is designed to dim after
a brief period of non-use.
A program will not run.
• Ensure the program is part of a sequence start and the start
has an active day schedule.
• If the program is part of a start sequence, ensure the priority
is not set to "0".
A satellite will not operate.
• Ensure the satellite address number is not set to "0".
• Ensure the satellite stations are assigned to a program, and
the program is part of a sequence start.
• Ensure the station run times are not set to "0", (using either
normal or syringe run time).
• Ensure the flow rate of a station does not exceed the set flow
capacity of the assigned Flow Zone.