ABB PEC 827E Product Manual
ABB PEC 827E Product Manual

ABB PEC 827E Product Manual

120 vac ac distribution shelf

Advertisement

Quick Links

PRODUCT MANUAL
PEC 827E
120 VAC AC Distribution Shelf
6180498P (23" For Conduit), 6180529P (23" W/Outlets)
6180542P (19" For Conduit), 6180533P (19" W/Outlets)
This document issue 4ge is updated with ABB brand and contact information only, no other content change from issue 4. Issue 4 release date: August 2007.
Page 1
© Copyright 2021 ABB. All rights reserved.

Advertisement

Table of Contents
loading

Summary of Contents for ABB PEC 827E

  • Page 1 6180498P (23” For Conduit), 6180529P (23” W/Outlets) 6180542P (19” For Conduit), 6180533P (19” W/Outlets) This document issue 4ge is updated with ABB brand and contact information only, no other content change from issue 4. Issue 4 release date: August 2007. Page 1...
  • Page 2: Table Of Contents

    3.5 Frame Ground Connection ......................14 4: Initial Turn On and Acceptance Procedures ..................15 4.1 General ............................15 5: AC Distribution Panel Ratings ......................15 Description Part Number T-Drawing for AC Distribution Shelf 4390670T Page 2 © Copyright 2021 ABB. All rights reserved.
  • Page 3: Foreword

    Please take a moment when the product is new to fill in this information. This data will allow faster service when calling ABB to order accessories, spare parts, or request field service. First, locate the product information label. This is typically located on the upper front of the equipment frame, or on the rear of the frame.
  • Page 4: Warnings

    4. Use of an attachment other than one approved by ABB will void any and all warranties, implied or other, and will increase risk of fire, or may possibly cause electrical shock, injury, or death to personnel.
  • Page 5: Cautions

    4. Before performing any maintenance, ensure AC or DC power is not applied to the plant. 5. Fuse holders, fuses, and circuit breakers are not to be loaded to more than 80 percent of their ampere rating. Page 5 © Copyright 2021 ABB. All rights reserved.
  • Page 6: 1: Installer Information

    1.3 Tools and Test Equipment Required for Installation and Acceptance Test Equipment Purpose Quantity Torque Wrench rated to 50 ft. pounds Torque connection points. Digital Meter Distribution verification Figure 1-1. AC Distribution Shelf (Front View) Page 6 © Copyright 2021 ABB. All rights reserved.
  • Page 7: 2: Mechanical Installation

    Install the side cover, top cover, and the bottom cover to the wire-way. Installation is complete. Figure 2-1. AC Distribution Shelf (Rear View) Figure 2-2. AC Distribution Shelf – Open Front Access Cover Page 7 © Copyright 2021 ABB. All rights reserved.
  • Page 8 Figure 2-3. AC Wire Way from 827E Inverter Shelf to AC Distribution Panel Page 8 © Copyright 2021 ABB. All rights reserved.
  • Page 9: 3: Electrical Connections

    See figure 3-2. Terminal Capacity Terminal Type Recommended Wire Size 6 AWG – 250 MCM Compression 6 AWG 6 AWG – 250 MCM 1/4" on 5/8” (Two Hole Lug) 6 AWG Page 9 © Copyright 2021 ABB. All rights reserved.
  • Page 10 Figure 3-1. 120 VAC From Inverter Shelf to AC Distribution Panel (Right Side) NEUTRAL LINE GROUND Figure 3-2: AC Distribution Shelf Input Connections Rear View (Unwired) Page 10 © Copyright 2021 ABB. All rights reserved.
  • Page 11 AC Input From Inverter Shelves Figure 3-3: AC Distribution Shelf Input Connections Front View (Fully wired) BUILDING GROUND Figure 3-4: Block AC Wiring diagram from the 827E Inverter shelves to the distribution shelf. Page 11 © Copyright 2021 ABB. All rights reserved.
  • Page 12: Load Connections

    Ground Connections Neutral Connections Line Connections Figure 3-5: Ground, Load, Neutral Connections Loads are routed under the Neutral connection and out the rear of the AC Figure 3-6: Load Connections cable routing Page 12 © Copyright 2021 ABB. All rights reserved.
  • Page 13: Load Connections (With Outlets)

    Terminal Capacity Terminal Type Recommended Wire Size 2 –15 Amps per position 4 - 14 AWG Compression Dependant on load Ground Neutral Load Figure 3-7: Ground, Load, Neutral Connections (With Outlets) Page 13 © Copyright 2021 ABB. All rights reserved.
  • Page 14: Frame Ground Connection

    Frame ground. See Figure 3-8. Terminal Type Recommended Wire Size 1/4” on 5/8” Centers for Inserts As Required Frame Ground Connection Figure 3-8: GEC Ground Connection Page 14 © Copyright 2021 ABB. All rights reserved.
  • Page 15: 4: Initial Turn On And Acceptance Procedures

    180 Amps 120VAC 15 Amps per circuit position 6180542P (19” For Conduit) 100 Amps 120VAC 70 Amps per circuit position 6180533P (19” W/Outlets) 100 Amps 120VAC 15 Amps per circuit position Page 15 © Copyright 2021 ABB. All rights reserved.
  • Page 16 With regard to and illustrations contained therein. Any reproduction, disclosure purchase orders, the agreed particulars shall prevail. ABB does to third parties or utilization of its contents – in whole or in parts not accept any responsibility whatsoever for potential errors or is forbidden without prior written consent of ABB.