Toshiba CV-10HB Instruction Manual page 20

High-voltage vacuum contactors
Hide thumbs Also See for CV-10HB:

Advertisement

TOSHIBA
(3) Service life of cap83citor
Opening and closing of the capacitor produces sever conditions for contactors,
such as high frequency inrush current and interpole recovery voltage more than
twice the normal voltage.
The criteria of the maximum number of the capacitor current switching operations
is shown in the graph below. The vacuum interrupter should be replaced when the
number of switching operations in the graph is reached.
s w i t c h i n g c u r r e n t (A)
Fig.9
Capacitor switching life
(with 6% reactor)
19