7.3.

CHANGE THE COM LOOP ADDRESS

If the COM loop address for 4466 must be changed, the address for 4464 and 4585 also must be changed (if mounted).
a) Disconnect the 4466 from the COM loop.
b) Reset the address for PCB 4464/4585 according to the instruction "RESET ADDRESS" in technical description for 4464 or
4585.
c) Set the new address manually for 4466.
d) Connect the 4466 to the COM loop.
e) Download SSD to the CIE. During download SSD, the 4464 and 4585 will get the correct addresses.