Download Print this page

Assembling And Connecting The Safety Ground Wire For Dc Power Supply And Poweredge Xr-Series Heater - Dell PowerEdge XR Series Instructions Manual

Advertisement

○ One UL 1015 10 AWG, 2-meter maximum (105/30 stranded) US NEC red (European IEC brown) wire (V DC return)
○ Two UL 1015 10 AWG, 2-meter maximum (105/30 stranded) US NEC green/yellow, green with a yellow strip (European
IEC green with a yellow strip) wire (safety ground)
● Two 90-degree ring-tongue terminals of M4 stud size suitable for 10 AWG insulated copper wire
● One power supply input plug PN: RN5T2 (supplied with DC power supply)
● One heater power cable assembly PN: 4YXNH (supplied with DC PowerEdge XR-series heater)
Topics:

1. Assembling and connecting the safety ground wire for DC power supply and PowerEdge XR-series heater

2. Assembling the power supply input plug to the heater power cable
3. Assembling the DC input power cable for PowerEdge XR-series heater
4. Connecting the -(48-60) V DC input power cable
1. Assembling and connecting the safety ground wire
for DC power supply and PowerEdge XR-series heater
About this task
NOTE:
This product is intended to be used in CBN (Common Bonding Network) applications.
Steps
1. Strip the insulation from the end of the US NEC green/yellow (European IEC green with a yellow strip) wire, exposing
approximately 0.175 inches (4.5 mm) of copper wire.
2. Using a hand-crimping tool, crimp the 90-degree ring-tongue terminal of M4 stud size (not supplied) and suitable for 10
AWG insulated copper wire to the US NEC green/yellow (European IEC green with a yellow strip) wire.
3. Remove the M4 nut and associated hardware from grounding post/stud.
4. Connect the safety ground to the grounding post/stud using the M4 nut, spring washer and locking/star washer.
5. An individual safety ground wire should be connected to the power supply and to the PowerEdge XR-series heater.
NOTE:
The system that is shown below is indicative only and may not match the actual system that you purchased.
Figure 1. Safety ground pin connection for DC power supply
1. Green/Yellow safety ground wire
3. Locking/star washer
5. M4 Nut
2. Grounding post/stud
4. Spring washer
Overview
5