OPTIONS FOR ABB DRIVES
FEPL-02 Ethernet POWERLINK adapter
module
Quick installation and start-up guide
Safety instructions
WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or
damage to the equipment can occur.
Mechanical installation
1. Pull out the lock.
2. Install the module carefully to an option
module slot of the drive. See the drive
hardware manual.
3. Push in the lock.
4. Tighten the screw to torque 0.8 N·m
using a Torx TX10 screwdriver.
WARNING! Do not use excessive force, or leave the screw too loose. Over-tightening can
damage the screw or module. A loose screw decreases the EMC performance, and can
cause an operation failure.
Electrical installation
Layout of the module
1
6
2
3
5
4
1
No.
Description
1
Lock
2
Mounting and grounding screw
3
RJ-45 connector [X1]
4
RJ-45 connector [X2]
5
Diagnostic LEDs
6
MAC address
3
4

Advertisement

loading

Summary of Contents for ABB FEPL-02

  • Page 1 — OPTIONS FOR ABB DRIVES FEPL-02 Ethernet POWERLINK adapter module Quick installation and start-up guide Safety instructions WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur. Mechanical installation 1.
  • Page 2 To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh. Further information See the latest version of FEPL-02 Ethernet POWERLINK adapter For more information on ABB fieldbus options and protocols, module user's manual (3AUA0000123527 [English]) in ABB library see the fieldbus communications web page (www.abb.com/drives/documents).