Wiring and equipment separations
Install all the wiring and controllers to minimize the possibility of accidental
contact with other potentially hazardous and disruptive power and lighting wiring.
Never place 24 VAC or communications wiring near other bare power wires,
lightning rods, antennas, transformers, or steam or hot water pipes. Never place
the wire in any conduit, box, channel, duct, or other enclosure containing power or
lighting circuits. Always provide adequate separation of communications and
another electrical wiring according to code. Keep wiring and controllers at least six
feet from large inductive loads (power distribution panels, lighting ballasts,
motors, etc.). Failure to follow these guidelines can introduce electrical
interference and cause the system to operate erratically.
Warning
By using this Honeywell literature, you agree that Honeywell will have no liability
for any damages arising from your use or modification to the literature. You will
defend and indemnify Honeywell, its affiliates, and subsidiaries from and against
any liability, cost, or damages, including attorneys' fees, arising out of or resulting
from any modification to the literature by you.
The material in this document is for information purposes only. The content and
the product it describes are subject to change without notice. Honeywell makes no
representations or warranties to this document. In no event shall Honeywell be
liable for technical or editorial omissions or mistakes in this document, nor shall it
be liable for any damages, direct or incidental, arising out of or related to the use of
this document. No part of this document may be reproduced in any form or by any
means without prior written permission from Honeywell.

2.1.1 Before Installation

1. Read these instructions carefully. Failure to follow them could damage the
2. Check the ratings given in the instructions and the product to ensure the
3. TR50 IAQ Sensor must be installed and mounted only by authorized and
4. When performing any work (installation, mounting, start-up), all manufacturer
5. It is recommended to keep the device at room temperature for at least 24 hours
6. After installation is complete, check out product operation as provided in these
Note: All wiring must agree with applicable codes, ordinances, and regulations as
specified in installation wiring diagrams.
TR50 - User Guide
product or cause a hazardous condition.
product is suitable for your application.
trained personnel.
instructions, particularly the Mounting Instructions (31-00566M-01), are to be
observed.
before applying power. This allows any condensation resulting from low
shipping/storage temperatures to evaporate.
instructions.