Outdoor Unit Clearance Requirements - LG MULTI V 5 Engineering Manual

Hide thumbs Also See for MULTI V 5:
Table of Contents

Advertisement

Outdoor Unit Installation Space
Proper airflow through the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet, and
outlet, and minimum allowable space requirements as illustrated in the diagrams below.
Description
Unit(s) is (are)
Enclosed by
Four (4) Walls
Unit(s) is (are)
Facing Away
From Each
Other
(To the Rear)
Two (2) Sides
Are Enclosed
By Walls
Different clearances are required if a Low Ambient Cooling Kit is installed. Refer to the Low Ambient Cooling Kit Installation Manual for clearance
information.
PLACEMENT CONSIDERATIONS
Installation Area
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
No Limitations on Wall Height
Front
No Limitations on Wall Height
Front
©

Outdoor Unit Clearance Requirements

Example No. 1
A and C 1"
A 1"
B 12"
C 1"
D 20"
A 1"
B 12"
C 1"
D 20"
E 1"
A 1"
B 20"
C 1"
D 20"
E 1"
F 36"
A 1"
B 12"
C 1"
D 12"
E 1"
F 20"
A 1"
B 20"
C 1"
D 20"
F 36"
A 1"
B 20"
C 1"
D 20"
E 1"
F 48"
A 1"
B 20"
C 1"
D 20"
E 1"
F 71"
A 1"
B 12"
A 8"
B 12"
E 16"
Example No. 2
A and C 2"
A 2"
B 4"
C 2"
D 20"
A 2"
B 4"
C 2"
D 20"
E 4"
A 2"
B 4"
C 2"
D 20"
E 4"
F 20"
A 2"
B 4"
C 2"
D 4"
E 4"
F 20"
A 2"
B 20"
C 2"
D 20"
F 24"
A 2"
B 20"
C 2"
D 20"
E 4"
F 36"
A 2"
B 20"
C 2"
D 20"
E 4"
F 48"
LIMITS / PLACEMENT | 99